Appendix
7.8
Record of Field Setting and Additional Refrigerant
Charge
Fill the following record and put it on the back side of electrical board.
Request for indication of setting contents, additional refrigerant charging amount and installation date
After filling out the below, please put it on the back side of an ex-board.
1. Record for setting contents
for the setting contents of
in the setting mode 2,
mark 8 in the right table.
2. Record for additional refrigerant charging amount
make sure to record the additional refrigerant charging amount.
(If do not use automatic refrigerant charging,
calculated and charge the additional refrigerant charging amount following as shown on the below.)
Additional charging amount
(Round off to one desimal place.)
3. Record of installation date
144
Night - Time low noise setting
~
External low noise level setting
Demand level setting
External low noise demand setting
High static pressure setting
Liquid pipe size (mm)
22.2
Ø
19.1
kg
Ø
15.9
Ø
12.7
Ø
9.5
Ø
6.4
Ø
OFF • Level 1 • Level 2 • level 3
Level 1 • Level 2 • level 3
Level 1 • Level 2 • level 3
OFF • ON
OFF • ON
Refrigerant amount for field piping
Refrigerant amount per 1m (kg/m)
0.37
0.26
0.18
0.12
0.059
0.022
Length of liquid pipe (m)
Total
=
X
=
X
X
=
=
X
=
X
X
=
General Information
SiEN34-705
3P176431