Mains Connection - BONFIGLIOLI agl 402 Quick Start Manual

Agile series
Table of Contents

Advertisement

Voorhout • Groningen • Weert • Hoogerheide
B

Mains connection

Danger!
Switch off power supply
Dangerous voltage: The power terminals may carry dangerous voltages for some time even if
the power supply is switched off. Wait for some minutes before starting to work at the
frequency inverter.
Make sure that the frequency inverter is de- energized.
Do not carry out high voltage insulation tests on cable connect to the frequency inverter.
Follow local wiring codes
Connect mains supply.
Type
3~400 V
kW
F1
A
L1, L2, L3
2
mm
PE
2
mm
or
Type
3~230 V
kW
0.18...0.75
F1
A
L1, L2, L3
2
mm
PE
2
mm
or
Type
1~230 V
kW
0.09...0.37
F1
A
L1, N
2
mm
PE
mm
2
or
Agile
Quick Start Guide
-02...-11
-13
0.25...1.5
2.2
6
10
1.5
2 x 1.5
1 x 10
-01...-07
-09
1.1
6
10
1.5
2 x 1.5
1 x 10
-01...-07
-09
0.55
6
10
1,5
2 x 1,5
1 x 10
T
I
+31(0)88 7865800
Note:
0,5
Nm
mm
AWG
-15
-18
-19
3.0
4.0
5.5
10
10
16
-11...-13
-15
1.5...2.2
3.0
16
25
-11...-13
-15
0.75...1.1
1.5
16
25
2,5
2 x 2,5
1 x 10
32
elsto.eu
Only required for DC-
link connection.
2
1,5
2,5
4
16
14
12
AWG: American Wire Gauge
(American unit)
-21
-22
-23
7.5
9.2
11
25
35
35
2.5
4
2 x 2.5
2 x 4
1 x 10
1 x 10
-18
-19
4.0
5.5
35
35
2.5
4
2 x 2.5
2 x 4
2 x 6
1 x 10
1 x 10
1x10
-18
-19
2.2
3.0
35
35
4
2 x 4
1 x 10
05/2013
10
8
-21
7.5
50
6
-21
3.0