Table 35: Output Mode Options - Bosch DS7200V2-EXP Installation Manual

Table of Contents

Advertisement

DS7200V2-EXP | Installation Guide | 3. Control Panel
Programming
Mode (Steady, Pulse, One Shot), Output ##
Address: See Table 33 on page 86
Default: See Table 33 on page 86
Selections: 1 to 13 (see Table 35)
There are two types of outputs: state-driven outputs and event-driven outputs. State-driven outputs
follow the state of a condition, either on or off. For example, a state-driven output is Type 0|1 Armed.
The output is active when the control panel is armed and inactive when the control panel is disarmed.
Event-driven outputs follow events when they occur. These events have no On or Off state. For
example, an event-driven output is Type 0|13 Ack Received. When the key is pressed, the output is
activated.
Table 35 describes the mode operation for both on-board and off-board outputs.
Table 35:
Output Mode Options
Mode
Mode Type
1
Steady
2
Latch
3
Toggle
4
Pulse
5
One-Shot
6
One-Shot
with Re-
Trigger
7
One-Shot
with Reset
8
Steady,
Reversed
Logic Normal
Bosch Security Systems, Inc. | 04/12 | F01U253045-02
Output
Type
State
Output turns on when the condition is active and turns off when the condition is
inactive.
Event
Output turns on when the event occurs. [System Reset] turns the output off.
State
Output turns on when the condition is active and remains on until [System Reset] is
pressed.
Event
Output turns on when the event occurs and remains on until [System Reset] is
pressed.
State
When the condition goes from inactive to active, the output changes state. The
condition going from active to inactive has no effect.
Event
Whenever the event occurs, the output changes state.
State
When the condition is active, the output pulses. When the condition is inactive, the
output is off.
Event
When the event occurs, the output pulses. The output remains pulsing until [System
Reset] is pressed.
State
When the condition changes from inactive to active, the output turns on. The output
turns off at the end of the One-Shot time. While the output is on, any changes in the
condition are ignored.
Event
When the event occurs, the output turns on and remains on for the One-Shot time.
When the output is on, a second event does not affect the output.
State
When the condition changes from inactive to active, the output turns on and remains
on for the One-Shot time. If the condition goes inactive and active again, the One-
Shot time is restarted and the output remains on.
Event
When the event occurs, the output turns on and remains on for the One-Shot time. If
a new event occurs when the output is on, the One-Shot time is restarted and the
output remains on.
State
When the condition changes from inactive to active, the output turns on and remains
on for the One-Shot time. If the condition goes inactive, the output is turned off early.
Event
When the event occurs, the output turns on and remains on for the One-Shot time.
[System Reset] turns the output off early.
State
Output turns on when the condition is inactive and turns off when the condition is
active.
Event
Output turns off when the event occurs. [System Reset] turns the output on.
Description