DS7200V2-EXP | Installation Guide | 2. System Installation
and Setup
2.3.3
Single Zone Configuration (Loops 1-8)
When wiring the on-board sensor loops in the
single zone configuration, install the resistor of
the appropriate value (2.2 kΩ resistors are
provided) at the far end of the sensor loop to
provide a reference for supervision. You can
connect dry contact sensing devices in series
(Normally-Closed) and/or in parallel (Normally-
Open) to any of these loops (see Figure 16).
Figure 16:
Single Zone Sensor Loop
Wiring
5
1
2
3
4
1- Sensor loop terminal
2- Common
3- Sensor loop terminal
4- Common
5- 100Ω maximum
6- 2.2 kΩ EOL resistor (P/N: 47819)
7- Normally-Open contacts
8- Combination of Normally-Open contacts and
Normally-Closed contacts
Loop resistance limits the number of Normally-
Open and/or Normally-Closed detection devices
that each sensor loop can supervise. The total
resistance for wire length and contacts, minus
the end-of-line resistor, must not exceed 100 Ω.
Bosch Security Systems, Inc. | 04/12 | F01U253045-02
6
7
8
2.3.4
Doubled Zone Configuration
When wiring the on-board sensor loops in the
doubled zone configuration, install the resistors
of the appropriate value (2.2 kΩ and 3.65 kΩ) as
shown in Figure 17. The control panel can be
configured to function with either Normally-Open
or Normally-Closed contacts. Normally-Closed
contacts are recommended.
Each sensor loop is monitored as a
separate zone.
Figure 17:
On-board Doubled Zone
Sensor Loop Wiring
1
7
6
1- Common
2- Sensor Loop 1 to Sensor Loop 8
3- On-board Locations 1 to 8
4- Alarm Contacts
5- 3.65 kΩ EOL resistor
6- 2.2 kΩ EOL resistor
7- On-board Locations 9 to 16
EN | 19
2
3
4
5