Figure 11: Maintained Keyswitch: Single Eol Resistor Configuration; Figure 12: Momentary Keyswitch: Single Eol Resistor Configuration; Figure 13: Keyswitch: Zone Doubled Configuration; Figure 14: Keyswitch: No Eol Resistor Configuration - Bosch DS7200V2-EXP Installation Manual

Table of Contents

Advertisement

DS7200V2-EXP | Installation Guide | 2. System Installation
and Setup
Keyswitch Wiring – Single EOL Configuration
For maintained switches, connect the EOL
resistor for the zone at the keyswitch so that the
switch opens the circuit when it operates. A
short on the circuit produces an alarm if the area
is armed and a trouble if it is disarmed. See
Figure 11.
Figure 11:
Maintained Keyswitch:
Single EOL Resistor
Configuration
1
2
1- Zone input
2- Common
3- 2.2 kΩ resistor
4- Keyswitch (Open on circuit arms area)
For momentary switches, connect the EOL
resistor for the zone at the keyswitch so that the
switch shorts the resistor when it operates. An
open on the circuit produces an alarm if the area
is armed and a trouble if it is disarmed. See
Figure 12.
Figure 12:
Momentary Keyswitch:
Single EOL Resistor
Configuration
1
3
2
1- Zone input
2- Common
3- 2.2 kΩ resistor
4- Keyswitch (Short on circuit toggles arming
state)
Bosch Security Systems, Inc. | 04/12 | F01U253045-02
4
3
4
Keyswitch Wiring – Zone Doubled
Configuration
For maintained or momentary operation, wire the
keyswitch as shown in Figure 13.
Figure 13:
Keyswitch: Zone Doubled
Configuration
1
5
2
1- Zone input
2- Common
3- Second zone wiring
4- 2.2 kΩ or 3.65 kΩ resistor
5- Keyswitch
Keyswitch Wiring – No EOL Resistor
Configuration
For maintained or momentary operation, wire the
keyswitch as shown in Figure 14.
Figure 14:
Keyswitch: No EOL Resistor
Configuration
1
2
1- Zone input
2- Common
3- Keyswitch
EN | 17
4
3
3

Hide quick links:

Advertisement

Table of Contents
loading