2.16 Keypad Programming - Bosch DS7200V2-EXP Installation Manual

Table of Contents

Advertisement

DS7200V2-EXP | Installation Guide | 2. System Installation
and Setup

2.16 Keypad Programming

2.16.1 Installer Mode/Installer Menu
A text keypad such as the DS7447E or
DS7447V2 LCD Keypad can be used
for keypad programming. The
DS7445i and DS7445V2 LED Keypads
cannot be used for keypad
programming.
Use of the Installer PIN might be
restricted. See Keypad Response
Options on page 75 for information on
enabling/restricting the Installer PIN.
There are three methods to access the control
panel's programming mode. Choose a method
from below and follow its subsequent steps:
1. From a text keypad:
a. Enter the Installer PIN. The default
Installer PIN is 9876. See Installer PIN on
page 69 for instructions on changing the
default Installer PIN.
b. Press [#][4][1] to enter the Installer
Menu.
c. Press [8] to enter the programming
mode.
2. From an Installer Keypad:
a. Set the Installer Keypad address to 0
(zero).
b. Connect the Installer Keypad to the
control panel. See Installer Keypad on
page 40 for instructions.
c. Close the Installer Switch.
d. Enter the Installer PIN.
e. Press [#][4][1] to enter the Installer
Menu.
f.
Press [8] to enter the programming
mode.
3. Without an Installer PIN:
a. Remove all power from the control panel
(Mains and standby battery).
b. Close the Installer Switch.
c. Connect the Installer Keypad to the
control panel if you are using an Installer
Keypad.
d. Restore all power to the control panel.
e. Locate the keypad displaying the Installer
Menu.
f.
Press [8] to enter the programming
mode.
Bosch Security Systems, Inc. | 04/12 | F01U253045-02
2.16.2 Expert/Installer Programming Modes
Installer Programming Mode: Installer
Programming Mode is the control panel's
default programming mode. This mode allows
the installer to access only a subset of the
available programming parameters. Installer
Programming Mode follows through the
addresses shown in this document.
Expert Programming Mode: When the
control panel enters the Expert Programming
Mode, all of the available programming
parameters can be accessed. The DS7200V2
Expert Programming Guide (P/N: 4998153891)
covers the expert set of parameters and
provides instructions on entering Expert
Programming Mode.
2.16.3 Parameter Addresses
Data for each parameter is stored at one or more
addresses. Special addresses identified as option
parameters allow you to set several options at a
single address.
There are two parts to every address displayed
across the keypad's top line:
Adr: XXXX: The number following "Adr"
indicates the current address displayed.
D=X: "X" indicates the data digit selection for
the address currently displayed.
Adr: 0000
To view a specific address, enter the 4-digit
address number and then press [#].
For example, to go to Address 0221, press the
following keys in this order: [0][2][2][1][#].
Leading zeroes can be omitted. Pressing
[2][2][1][#] is the same as pressing
[0][2][2][1][#].
Adr: 0000
0221
To scroll forward one address at a time, press
[#]. To scroll back one address at a time, press
[*].
EN | 45
D=0
D=0

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents