Bosch DS7200V2-EXP Installation Manual page 106

Table of Contents

Advertisement

DS7200V2-EXP | Installation Guide | 3. Control Panel
Programming
Keypad/Door Access Control Module (DACM) Area Options
Address:
Keypad/DACM 1: 0679
-
Keypad/DACM 2: 0681
-
Keypad/DACM 3: 0683
-
Keypad/DACM 4: 0685
-
Keypad/DACM 5: 0687
-
Keypad/DACM 6: 0689
-
Keypad/DACM 7: 0691
-
Keypad/DACM 8: 0693
-
Default:
Keypad/DACM 1: 1 (Device is a keypad/DACM assigned to Area 1)
-
Keypads/DACMs 2 to 8: 0 (No keypad/DACM assigned)
-
Selections: 0 to 4, 9 to 12
Keypad/DACM Area Options
Keypad/DACM not assigned (disabled)
Assign Keypad/DACM to Area 1
Assign Keypad/DACM to Area 2
Assign Keypad/DACM to Area 3 (DS7240V2
only)
Assign Keypad/DACM to Area 4 (DS7240V2
only)
Device is a Keypad
Device is a DACM
This parameter identifies the device connected to the control panel's Data Bus (Addresses 1 to 8) as a
DACM, and assigns the DACM to an area.
The control panel supervises the connection to the DACM. If it fails to communicate with the control
panel, the control panel sends a "DBus Missing" {125} report.
DACM Location Assignment
Address:
DACM 1: 3546 to 3547
-
DACM 2: 3548 to 3549
-
DACM 3: 3550 to 3551
-
DACM 4: 3552 to 3553
-
DACM 5: 3554 to 3555
-
DACM 6: 3556 to 3557
-
DACM 7: 3558 to 3559
-
DACM 8: 3560 to 3561
-
Default: 0,0
Selections:
DS7240V2: 0,0 to 4,0
-
DS7220V2: 0,0 to 2,4
-
A DACM door contact can occupy any location in the control panel. Use this parameter to assign a
control panel location to a DACM door contact.
Bosch Security Systems, Inc. | 04/12 | F01U253045-02
Enter This Data Digit to Select Options
0 1
2 3 4 5 6 7 8 9 10 11 12 13 14 15
EN | 106