D8024 Analog Fire Alarm Control Panel Operator’s Guide POWER SYSTEM TROUBLE Enable Keypad TROUBLE SILENCED System Trouble Alarm Manual Reset Silenced Silence Alarm ALARM SILENCED Disable Keypad POINT BYPASSED ALARM D8024 National Security Systems (800)457-1999 http://www.nationalsecuritysystems.com...
D8024 Contents Contents Notices ....................................5 General Notices ..................................5 FCC Notice .................................... 5 1.2.1 Part 15 ....................................5 UL/NFPA Notice ..................................5 Overview ....................................7 System Overview .................................. 7 Control Level Distinction ..............................8 Passcodes ..................................... 8 Controls and Displays ................................8 Control Level 1 (Display Functions) ..........................
Page 4
D8024 Figures and Tables Figures Figure 1: D8024 Fire Alarm Control Panel ............................7 Figure 2: D8024 Front Panel Display, Hinged Panel Open ....................... 9 Figure 3: System Event and Status LED Display ..........................9 Figure 4: Control Level 2, Entry Menu 1 ............................13 Figure 5: Control Level 2, Entry Menu 2 ............................
D8024 Notices Notices General Notices These instructions contain procedures to follow in order to avoid personal injury and/or damage to the equipment. NFPA 72 requires a complete system-wide functional test be performed following any modifications, repair, upgrades or adjustments made to the system’s components, hardware, wiring, programming and software/ firmware.
D8024 Overview Overview System Overview Radionics’ D8024 Analog Fire Alarm Control Panel (FACP) is an expandable control panel that provides point identification through addressable analog devices. The D8024 has two expansion slots to accommodate plug-in polling circuit modules. Each of these polling circuit modules can support up to 126 analog addresses, giving the panel a potential of 252 addressable points.
D8024 Overview Control Level Distinction The D8024 has three available control levels. At all three levels, the LED display indicates condition; the Zone/Area LEDs indicate location and identified alarm/trouble information is displayed alphanumerically. • Control Level 1 (Display Level): Inhibits the system control keys, limiting the front panel function to annunciation. •...
D8024 Overview The alphanumeric keys normally function as number keys. They can be toggled to letter keys by pressing the [Change] key at the right end of the alphanumeric key row. The [Shift] key at the left end of the alphanumeric keys toggles between the upper and lower row of letters.
D8024 Overview System Event and Status LED Function An input point is in alarm state, or has latched into an alarm state. This clears Alarm when the system is reset. There is a fault in the system: SLC wiring, power fault, etc. This clears when the System Trouble fault has been corrected and the panel has been reset.
D8024 Control Level 1 Control Level 1 (Display Functions) At Control Level 1, the control keys are disabled and the control panel functions only as an annunciator. Pressing any of the control keys will result in a series of interactive messages on the alphanumeric display that end in a prompt for a Control Level 2 passcode.
D8024 Control Level 2 Control Level 2 (Controller Functions) At Control Level 2, the control panel functions as a Controller (see Section 2.2 “Control Level Distinction”). To enable the control keys (to enter Control Level 2), open the hinged panel and press the [Shift] key. The alphanumeric display shows the following prompt: [Panel ACTIVE control keys INHIBITED] Do you want to enable the control keys?
D8024 Control Level 2 Trouble Conditions The system responds to other-than-normal conditions that are not caused by alarms by sounding the internal buzzer and initiating a Trouble Condition. 4.2.1 Trouble Signals If a device fails to respond, is disabled, the response is not within the normal parameters, or the system detects a fault, the amber System Trouble or Fault LED will light.
D8024 Control Level 2 4.3.2 Alarm Signal Response Press the [Alarm Silence] key to turn off all external NAC devices. The Alarm Silenced LED will light. Pressing the [Alarm Silence] key again turns on all external NAC devices. Press the [Trouble Silence] key to turn the panel buzzer off. The amber Trouble Silenced LED will light. Press the [System Reset] key to reset the system.
D8024 Control Level 2 4.4.1.3 Zones Test Press the [3] key to select Zones. The Zones Test allows the operator to test devices on the polling circuit(s) and peripheral device circuit(s) without having to reset the panel after each device is tested. Note: If no action is taken within one minute, the display reverts to the normal display.
D8024 Control Level 2 4.4.2 Time Setting Select the third option from the Main Menu, 3) Time, to change the time displayed on the D8024. 4.4.3 Enable/Disable Functions Main Menu option four, 4) Enable, opens the Enable Menu. Main Menu option five, 5) Disable, opens the Disable Menu. ENABLE: 1) Zone 2) Input...
D8024 Control Level 2 4.4.3.4 Enable/Disable Delayed Day Mode The Delayed Day Mode is configured from Control Level 3. This mode causes the panel to respond to high sensor signals by sounding the panel buzzer and displaying a warning message at the alphanumeric display. The panel delays alarm activation for a programmed period.
D8024 Control Level 2 4.4.4 View Functions Select 7) View from the Main Menu to enter the View Menu. This menu displays information about the selected option on the alphanumeric display. After viewing an option, press the [No] key to return to the View Menu. Press the [No] key again to return to the Main Menu.
D8024 Control Level 3 Control Level 3 (Programmer Functions) Note: Commission, configure, networking and certain disable options are not available to Control Level 2 operators. These options are reserved for Control Level 3 operators. See the Analog Fire Alarm Control Panels Programming Guide (P/N: 38789) for complete information on commissioning and programming the D8024 Analog FACP.
D8024 Index Index Menus Control Level 2, Entry Menu 1 ........ 13 Alarm Signal Response ..........15 Control Level 2, Entry Menu 2 ........ 13 Alarm Signals ............... 14 Enable Menu ............13 Enable/Disable Menus ..........17 Alphanumeric and Program/Interactive Key Functions 9 Main Menu ..........13, 15, 17, 18 Outputs Menu ............