DS7200V2-EXP | Installation Guide | 2. System Installation
and Setup
Do not tie the black (-) output to
earth ground when using any external
power supply. A ground fault
condition is reported if black (-) is
grounded.
2.7.5
DX3010 Addressing
Any time you change the address DIP
switches, cycle the power to the
module OFF and then ON for the
changes to take effect.
Each DX3010 module connected to the control
panel must have its own address DIP switches
set as shown in Table 12.
Set the address DIP switches as shown in Table
12.
Shaded rows apply only to the DS7240V2.
Table 12:
DX3010 Address DIP Switch
Settings
Data Bus
DX3010 DIP Switches
Address
1
2
150
OPEN
OPEN
(Outputs
5 to 12)
151
CLOSE
OPEN
D
(Outputs
13 to
20)
See Figure 43 for DX3010 DIP switch
configuration.
Figure 43:
DX3010 DIP Switch
Configuration
1
2
1 2 3 4 5 6
1- OPEN (Up) position
2- CLOSED (Down) position
Sample address setting shown is for Address
150
Bosch Security Systems, Inc. | 04/12 | F01U253045-02
4
8
16
MODE
OPEN
OPEN
OPEN
CLOSE
D
OPEN
OPEN
OPEN
CLOSE
D
=
=
OPEN
2.7.6
DX3010 Supervision
The control panel supervises communication to
the DX3010. If it fails to communicate with the
DX3010, it sends a "DBus Missing" {125} report.
2.8
RS-232 Serial Interface Setup
(DX4010i/DX4010)
There are some board layout
differences between the DX4010i and
the DX4010. However, the two
modules wire, program, and operate
the same. The figures in this section
show the DX4010i's board.
2.8.1
Overview
Both modules are RS-232 serial interface
modules that connect a standard serial printer, or
other serial device, to the control panel. They can
also be used for a RPS local programming direct
connection. The DX4010i is a DTE serial interface
module. Depending on which device you have,
see the DX4010i Installation Guide (P/N:
4998141106) or the DX4010 Installation Guide
(P/N: 49539) for complete installation,
addressing, and operating instructions.
2.8.2
DX4010i/DX4010 Wiring
These modules contain static-
sensitive components. Follow anti-
static procedures when handling this
module.
Both modules are shipped in a plastic enclosure
that can be placed on a desktop or similar
surface.
Distance from the control panel is determined by
the total combined wire length of all devices
(including keypads) connected to the control
panel's Data Bus terminals.
See Table 13 for combined total wire length.
Table 13:
DX4010i/DX4010 Wire
Lengths
Power
Source
DX4010i
Control Panel
/DX4010
External
to
Power Supply
Control
Panel
EN | 31
0.8 mm
1.2 mm
(#22 AWG)
(#18
AWG)
305 m
610 m
(1007.7 ft)
(2001 ft)