Table 36: Pulse Mode Configuration; Table 37: One Shot Mode Configuration - Bosch DS7200V2-EXP Installation Manual

Table of Contents

Advertisement

DS7200V2-EXP | Installation Guide | 3. Control Panel
Programming
Steady, Pulse, and One-Shot Mode Configuration
Steady and Toggle Modes: These modes are not affected by the Time Base and Time Multiplier
parameters (see Table 36 and Table 37).
Pulse Modes: The system calculates the On Time (activation) and the Off Time for outputs based
on the values in the Base and Multiplier columns (see Table 36). The duration, or On Time, of an
output is determined by selecting one of the four Base options from Table 36. Calculate the Off
Time by multiplying the Base by the Multiplier.
The Time Base of 200 ms in Table 36 and Table 37 is only available for on-board outputs.
Table 36:
Pulse Mode Configuration
Base
(On Time = Time of
0
1 (200
ms)
2 (1 sec)
3 (1 min)
4 (1 h)
One Shot Modes: The duration of the On Time of a One Shot output is determined by multiplying
the Base by the Multiplier.
Table 37:
One Shot Mode Configuration
Base
Multiplie
r
0
N/A
1 (200
01 to 99
ms)
2 (1 sec)
01 to 99
3 (1 min)
01 to 99
4 (1 h)
01 to 99
Bosch Security Systems, Inc. | 04/12 | F01U253045-02
On Time
Multiplie
r
Base)
0
N/A
200 ms
01 to 99
1 sec
01 to 99
1 min.
01 to 99
1 h
01 to 99
On Time
(On Time = Base x
Multiplier)
0
200 ms to 19.8 sec
1 to 99 sec
1 to 99 min.
1 to 99 h
Off Time
(Off Time = Base x
Multiplier)
Always Off
200 ms to 19.8 sec
1 to 99 sec
1 to 99 min.
1 to 99 h
Tolerance
N/A
±200 ms
±1 sec
±1 min.
±1 h
EN | 95
Tolerance
N/A
±200 ms
±1 sec
±1 min.
±1 h

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents