Bosch DS7200V2-EXP Installation Manual page 85

Table of Contents

Advertisement

DS7200V2-EXP | Installation Guide | 3. Control Panel
Programming
RF ID for Location ##, Device
You must exit control panel programming in order to enter the RF ID code. Add RF ID codes after you
complete your programming session. See Adding RF ID Codes on page 42 for complete instructions.
RF Transmitters and Zone States
With the exception of the door/window transmitter, all RF transmitters show only two electrical zone
states (Normal and Faulted).
The RF3401E Point Transmitter can monitor both a reed switch (magnet) and a supervised
sensor loop. After the door/window transmitter's ID is added, the control panel shows one
of the following status messages depending on how the door/window transmitter is
configured:
­
"No magnet, no loop": the reed switch is open (no magnet is present), and there is no
device connected to the sensor loop
­
"Reed switch closed": the reed switch is closed by a magnet
­
"Loop closed": a device is connected to the sensor loop
­
"Reed closed, loop closed": the reed switch is closed by a magnet, and a device is
connected to the sensor loop
The RF3405E Inertia Transmitter operates similarly as the RF3401E described above,
however the RF3405E can monitor both a reed switch (magnet) and a supervised sensor
loop or a reed switch and an inertia sensor loop. It cannot monitor a supervised sensor
loop and an inertia sensor loop.
For this example, mount the point transmitter on a doorjamb, and mount its magnet on the door.
Close the door to place the magnet next to the reed switch. The control panel now recognizes the
reed switch to be in a normal (not faulted) state. From this point forward, it shows the zone
(door/window transmitter) as shorted (faulted) whenever it sees the reed switch faulted. It shows the
zone as normal when the reed switch returns to normal, even though the sensor loop remains faulted.
To continue with this example, connect a contact on a window near the door. Wire the contact and
the EOL resistor to the Door/Window transmitter's sensor loop and close the window. The control
panel now recognizes the sensor loop to be in a normal (not faulted) state. From this point forward, it
shows the zone (door window transmitter) as faulted whenever it sees either the sensor loop or the
reed switch faulted. It only shows the zone as normal when both the reed switch and the sensor loop
return to normal. When only the reed switch is monitored, only the Normal and Shorted (Faulted)
zone states are shown.
Cut out reed switch if not used.
Disabling a Zone (RF or Wired)
To disable a wired or wireless (RF) zone, do any of the following:
Set the location's device parameter to 0 (zero). See Location ##, Device on page 82.
Set the location's zone function parameter to 0 (zero). See Location ##, Zone Function on page 83.
Set the location's area parameter to 0 (zero). See Location ##, Area on page 83.
Bosch Security Systems, Inc. | 04/12 | F01U253045-02
EN | 85

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents