numbers 60-746-01, 60-803, 60-804, 60-820, 60-983, 60-984, 60-985, and 600-1020. UL requirements take
priority over SIA requirements.
SIA setting requirements
Table 1 describes programming requirements to meet ANSI-SIA CP-01.
Table 1.
SIA setting requirements
Shortcut #
Function
0013 - 0063
Exit extension
0016 - 0066
Duress code
02006
Dialer abort delay
02007
Cancel message
02009
Call wait cancel
0310 - 0360
Entry delay
0311 - 0361
Exit delay
06015
Swinger limit
1100
Smoke verify
N/A
Cross-zoning
Table 2 describes nonprogrammable (hard coded) system operation as required to meet ANSI-SIA CP-01 and
is provided only for your reference.
Table 2.
ANSI-SIA CP-01 requirements
Function
SIA false alarm
Auto stay arming
Disarm during entry delay
Cancel alarm
Abort annunciation
Entry/exit progress annunciation
Note:
You may use the silent arming feature to suppress arming level and exit beeps for the current arming period. Refer to
the Concord 4 User Manual (466-2183) for more information on silent arming.
Programming
Testing page
page reference
reference
29
70
30
70
35
70
36
70
36
70
40
70
40
70
46
70
58
70
91
70
Operation
Enabled
Enabled
Enter code only (or 1 + CODE)
Enter code only (or 1 + CODE)
Enabled
Enabled
Default setting Required setting
On
On
Disabled
Disabled
30 Sec.
15 to 45 sec.
On
On
Disabled
On if reporting to central
station and customer has call
waiting service
30 sec.
30 to 240 sec.
60 sec.
45 to 184 sec.
1
1
Off
On if smoke alarms are
programmed into system
Disabled
Enabled for zones with a high
probability of false alarms