Household burglary alarm system unit (UL 1023)
Basic system plus the following:
•
Hardwired magnetic contact (13-068 or 13-071) or wireless learn mode door/window sensor (60-362).
•
Immediate beeps set to on.
•
UL 98 options set to on.
•
Receiver failure set to on (if wireless devices are used).
•
Siren verify set to on.
•
Exit delay set to 60 seconds.
•
Quick exit set to off.
•
Siren timeout set to 4 minutes or more.
•
Entry delay set to 45 seconds or less.
•
RF Tx timeout set to 24 hours (if system includes a built in receiver or SuperBus 2000 RF receiver or
SuperBus 2000 RF transceiver and wireless burglary sensors).
•
Extended delay set to off.
•
Sleep time set to off.
•
Two trip error set to off.
•
Alarm verify set to off.
•
Disable trouble beeps set to off.
Household fire warning system (UL 985)
Basic system plus the following:
•
Wireless smoke sensor 60-506-319.5 or 60-848-02-95 learned into sensor group 26.
•
Immediate beeps set to on.
•
UL 98 options set to on.
•
Receiver failure set to on (if wireless devices are used).
•
Siren verify set to on.
•
RF Tx timeout set to 4 hours (if system includes a built-in receiver or SuperBus 2000 RF transceiver
and wireless smoke sensors).
•
Sleep time set to off.
•
Siren timeout set to 4 minutes or more.
•
Two-trip error set to off.
•
Disable trouble beeps set to off.
UL 1023 and 985 24-hour backup
For 24-hour backup, the total current draw for all connected devices is limited to 90 mA (during normal
standby conditions) using a 4.5 or 5.0 Ah battery, or 190 mA (during normal standby conditions) using a 7.0
Ah battery.
SIA system requirements
SIA system requirements are the same as those described for a UL listed basic system on
installations
on page 2. If multiple annunciation is required, use additional touchpads. This applies to model
Chapter 1
Introduction