66
Concord 4
Installation Manual
Phone test freq. (0303)
Default setting is 7 days.
This setting determines how often the panel conducts the automatic phone test (see
on page 59). The system can be set to perform an automatic phone test anywhere from every day to
SETTINGS
every 255 days.
Note:
For UL 1610 and 1635 listed installations, this feature must be set to 1.
To set the Phone test freq, do the following:
1. With the display showing PHONE TEST FREQ nnn DAYS (current setting), enter the number of
days (1 to 255).
2. The display flashes the entered setting. Press # and the display shows the new setting.
Next phone test (0304)
Default setting is 7 days.
This setting is used by the Automatic phone test feature under
determine when the next automatic phone test should occur. This setting should be the same as, or less than, the
Phone test freq. setting.
Note:
For UL 1610 and 1635 listed installations, this feature must be set to 1.8.
To set the Next phone test, do the following:
1. With the display showing NEXT PHONE TEST nnn DAYS (current setting), enter the number of
days (1 to 255).
2. The display flashes the entered setting. Press # and the display shows the new setting.
Output trip time (0305)
Default setting is 4 seconds.
This setting determines how long outputs are activated when tripped (if they are configured for a momentary
response). To set the Output trip time, do the following:
1. With the display showing OUTPUT TRIP TIME nn SECS (current setting), enter the number of
seconds (1 to 12).
2. The display flashes the entered setting. Press # and the display shows the new setting
P
Phone options - global settings
-
HONE OPTIONS
GLOBAL
on page 59 to