Chapter 8 SPECIFICATIONS

8.1 Standard Models

8.1.1 Three-phase 200 V Series

*1 Fuji's 4-pole standard
*2 The rated capacity is for 220V output voltage.
*3 Output voltages cannot exceed the power supply voltage.
*4 Use the inverter at the current given in ( ) or below when the carrier frequency command is higher than
4 kHz (F 26 =4 to 15) or the ambient temperature is 40°C or higher.
*5
Interphase
voltage
unbalance
If this value is 2 to 3 %, use an AC reactor (ACR).
*6 Tested under the standard load condition (85% load for applicable motor rating).
*7 Calculated under Fuji-specified conditions.
*8 Indicates the value when using a DC reactor (option).
*9 Average braking torque obtained with the AVR control off (F 05 =0). (Varies according to the efficiency
of the motor.)
*10 Average braking torque obtained by use of an external braking resistor (standard type available as
option).
*11 To make FRENIC-Mini compliant with category TYPE1 of the UL Standard (or NEMA1), an optional
NEMA1 kit is required. Note that the TYPE1-compliant FRENIC-Mini should be used in the ambient
temperature range from -10 to +40°C.
Note: A box ( ) in the above table replaces A, C, E, or J depending on the shipping destination.
Max.voltag
e
(V)
-
Min.voltag
(%)
=
3
-
phase
average
8-1
e
(V)
×
67
(Refer
voltage
(V)
to
IEC
61800
-
3
(5.2.3))