FujiFilm Frenic-Mini Instruction Manual page 52

Controller
Table of Contents

Advertisement

If you press the
or
appear:
Frequency
Frequency
setting from
command 1
communica-
(F01)
tions link
0
Disabled
Other than the above
(3) Monitor the Running Status
In Running mode, the seven items listed below can be monitored. Immediately after the inverter is
turned on, the monitor item specified by function code E43 is displayed. Press the
between monitor items.
Monitor Items
Speed monitor
(Hz, rpm, m/min, min)
Output current (A)
Input power (kW)
Output voltage (V)
PID process command (Note 1)
PID feedback amount (Note 1)
Timer (sec) (Note 1)
(Note 1) The PID process command and PID feedback amount are displayed only under the PID
control using a process command (J01 = 1 or 2). Further, the timer (for timer operation) is
only displayed when timer is enabled (C21 = 1).
(Note 2) The dot in the lowest digit will blink.
(Note 3) The dot in the lowest digit will light.
(Note 4) A positive integer is displayed.
key in any conditions other than those described above, the following will
Multistep fre-
quency setting
Disabled
Table 3.3 Monitor Items
Display Sample on
the LED monitor
50.00
1.90A
0.40P
200U
10.00.
(Note 2)
9.00.
(Note 3)
6
(Note 4)
PID control can-
Displayed using
celled
PID enabled
Frequency setting by keypad
Cancelled
PID output (as final frequency set-
PID enabled
ting)
Manual speed command currently
Cancelled
selected (frequency setting)
Meaning of Displayed Value
Refer to Table 3.4.
Detected output current.
A
: An alternative expression for A (ampere)
Detected input current to the inverter in Amp.
P : An alternative expression for kW (kilo watt)
Commanded output voltage.
U
: An alternative expression for V (voltage)
(PID process command or PID feedback
amount) ⌠ (PID display coefficient A – B) + B
PID display coefficients A and B: Refer to
function codes E40 and E41
Remaining effective timer count
3-9