FujiFilm Frenic-Mini Instruction Manual page 38

Controller
Table of Contents

Advertisement

Symbol
Name
[X1]
Digital
(1) The various signals such as coast-to-stop, alarm from external equip-
input 1
[X2]
Digital
input 2
(2) Input mode, i.e. Sink/Source, is changeable by using the internal
[X3]
Digital
input 3
(3) Switches the logic value (1/0) for ON/OFF of the terminals between
[FWD]
Forward
operation
command
[REV]
Reverse
(4) The negative logic signaling cannot be applicable to [FWD] and [REV].
operation
command
Digital input circuit specifications
[PLC]
PLC
Connects to PLC output signal power supply. (Rated voltage: +24 VDC,
Maximum output current: 50 mA)
signal
power
[CM]
Digital
Common terminal for digital input signals
common
This terminal is electrically isolated from terminals [11] and [Y1E].
Table 2.8 Continued
ment, and multistep frequency selection can be assigned to terminals
[X1] to [X3], [FWD] and [REV] by setting function codes E01 to E03,
E98, and E99. For details, refer to Chapter 5, Section 5.2 "Overview of
Function Codes."
jumper switch.
[X1] to [X3], [FWD] or [REV], and [CM]. If the logic value for ON be-
tween [X1] and [CM] is 1 in the normal logic system, for example, OFF
is 1 in the negative logic system and vice versa.
2-17
Functions
Item
Operation
ON level
voltage
OFF level
(SINK)
Operation
ON level
voltage
(SOURCE) OFF level
Operation current at ON
(Input Voltage at 0 V)
Allowable leakage
current at OFF
Min.
Max.
0V
2V
22V
27V
22V
27V
0V
2V
2.5mA
5mA
-
0.5mA

Advertisement

Table of Contents
loading

Table of Contents