Select 3-wire operation command--(HLD)
(Function code data = 6)
Digital input signal (HLD) may self-hold the forward (FWD)/reverse (REV) run
commands given at the external signal input terminals to enable 3-wire inverter
operation.
Shorting the circuit between the (HLD)-assigned terminal and terminal [CM] will
self-hold the (FWD) or (REV) command. Opening the circuit will release the hold.
Coast-to-stop command--(BX)
(Function code data = 7)
Shorting the circuit between the (BX)-assigned terminal and terminal [CM] will
immediately stop the inverter output so that the motor will coast to a stop without
issuing any alarms.
Reset alarm--(RST)
(Function code data = 8)
When the protection function has been activated (the inverter is in Alarm mode),
shorting the circuit between the (RST)-assigned terminal and terminal [CM] will
reset the alarm output on terminals [Y1] and [30A,B,C]. Opening the circuit will
release all the alarm indications to restart operation. Allow 10 ms or more for the
short-circuit time.
(RST) should be kept off for normal inverter operation.
Alarm from external equipment--(THR)
(Function code data = 9)
When the motor is running, opening the circuit between the (THR)-assigned ter-
minal and terminal [CM] will immediately stop the inverter output and issue the
OH2
alarm "
." The motor will coast to a stop.
Ready for jogging--(JOG)
(Function code data = 10)
Turning on the (JOG) command makes the motor ready for jogging. Use this
command for fine adjustment to position a workpiece, for example.
When the motor is ready for jogging with (JOG) being on, pressing the
turning the (FWD) or (REV) command on will start the motor to jog.
If the
key is released, the motor will decelerate to a stop.
Jogging operation follows the settings of:
- Jogging frequency set by function code C20
- Acceleration or deceleration time set by function code H54
5-31
key or

Advertisement

Table of Contents