FujiFilm Frenic-Mini Instruction Manual page 136

Controller
Table of Contents

Advertisement

E 6
[ 15 ]
Operation protection
Problem
An error occurred due to incorrect operation of the motor.
Possible Causes
(1) The
key was pressed
when H96 = 1 or 3.
(2) The start check function
was activated when H96
= 2 or 3.
E 8
[ 16 ]
RS485 communications error
Problem
A communications error occurred during RS485 communications.
Possible Causes
(1) Host controllers (e.g.,
PLCs and personal
computers) did not
operate due to incorrect
settings and/or defective
software/hardware.
(2) Relay converters (e.g.,
RS232C/RS485
converter) did not operate
due to incorrect
connections and settings,
and defective hardware.
(3) Broken communications
cable or poor contact.
(4) Even though no response
error detection time (y08)
has been set,
communications did not
occur cyclically.
(5) A high intensity noise was
given to the inverter.
What to Check and Suggested Measures
Change the setting for H96 so that the STOP key priority
function is invalid to ensure that the inverter does not
operate unexpectedly.
Check that E 6 occurs when:
- The power is switched on
- An alarm is released (by pressing the
reset alarm (RST) on)
- The link command (LE) has switched the inverter
operations.
Reconsider the running sequence to avoid input of the run
E 6
command when
Change the setting for H96 so that the STOP key priority
function is invalid to ensure the inverter does not operate
unexpectedly.
(To reset the alarm, turn the run command off.)
What to Check and Suggested Measures
Check the controllers.
Remove the cause of the controller error.
Check the converter (e.g., check for poor contact).
Change the various converter settings, reconnect the
wires, or replace hardware (such as recommended
devices) as appropriate.
Check continuity of the cable, contacts and connections.
Replace the cable.
Check the host controllers.
Change the settings of host controller software, or make
the no response error detection time invalid (y08=0).
Check if appropriate noise control measures have been
implemented (e.g., correct grounding and routing of control
and main circuit wires).
Improve noise control.
Improve measures against noise from host controllers.
Replace the relay converter with a recommended insulated
converter.
6-17
has occurred.
key or turning