11.1 Compliance with UL Standards and Canadian Standards (cUL certification)
11.1.1 General
Originally, the UL standards were established by Underwriters Laboratories, Inc. as private criteria
for inspections/investigations pertaining to fire/accident insurance in the USA. Later, these
standards were authorized as the official standards to protect operators, service personnel and the
general populace from fires and other accidents in the USA.
cUL certification means that UL has given certification for products to clear CSA Standards. cUL
certified products are equivalent to those compliant with CSA Standards.

11.1.2 Considerations when using FRENIC-Mini in systems to be certified by UL and cUL

If you want to use the FRENIC-Mini series of inverters as a part of a UL Standards or CSA
Standards (cUL certified) certified product, refer to the related guidelines described on page viii.
11.2 Compliance with European Standards
The CE marking on Fuji products indicates that they comply with the essential requirements of the
Electromagnetic Compatibility (EMC) Directive 89/336/EEC issued by the Council of the European
Communities and Low Voltage Directive 73/23/EEC.
Only the EMC filter built-in type of inverters that bear a CE marking are compliant with these EMC
Directives.
Inverters that bear a CE marking or TÜV mark are compliant with the Low Voltage Directive.
The products comply with the following standards:
Low Voltage Directive
EMC Directives
CAUTION
The FRENIC-Mini series of inverters are categorized as a "restricted sales distribution class" of the
EN61800-3. When you use these products with any home appliances or office equipment, you may
need to take appropriate countermeasures to reduce or eliminate any noise emitted from these
products.
EN50178:
1997
EN61800-3:
1996+A11 : 2000
EN55011:
1998+A : 1999
Immunity:
Second environment (EN61800-3+A11 Industrial)
Emission:
Class 1A (EN55011+A1)
(Applicable only to the EMC filter built-in type of inverters)