FujiFilm Frenic-Mini Instruction Manual page 67

Controller
Table of Contents

Advertisement

LED Monitor
Display contents
shows:
5_00
Accumulated
run time
5_01
DC link circuit
voltage
5_03
Max. temperature
of heat sink
5_04
Max. effective
current
5_05
Capacitance of
the DC bus
capacitor
5_06
Accumulated
run time of
electrolytic
capacitor on the
printed circuit
board
5_07
Accumulated
run time of the
cooling fan
5_08
Number of
startups
5_11
No. of RS485
errors
5_12
RS485 error
contents
5_14
ROM version of
inverter
5_16
ROM version of
keypad panel
Table 3.13 Maintenance Display Items
Shows the accumulated power-ON time of the inverter.
Unit: thousands of hours.
When the total ON-time is less than 10,000 hours (display: 0.001 to
9.999), it is possible to check data in hourly units. When the total
time is 10,000 hours or more (display: 10.00 to 65.53), the display
will change to units of 10 hours. When the total time exceeds 65,535
hours, the display will be reset to 0 and the count will start again.
Shows the DC link circuit voltage of the inverter.
Unit: V (volts)
Shows the maximum temperature of the heat sink for every hour.
Unit: ºC
Shows the maximum effective current for every hour.
Unit: A (amperes)
Shows the current capacitance of the DC bus capacitor, based on
the capacitance when shipping as 100%. Refer to Chapter 7 "MAIN-
TENANCE AND INSPECTION" for details.
Unit: %
Shows the accumulated run time of the capacitor mounted on the
printed circuit board.
The display method is the same as for "accumulated run time"
above.
However, when the total time exceeds 65,535 hours, the count stops
and the display remains at 65.53.
Shows the accumulated run time of the cooling fan.
The cooling fan ON/OFF control (function code H06) is effective, so
the time when the fan is stopped is not counted.
The display method is the same as for "accumulated run time"
above.
However, when the total time exceeds 65,535 hours, the count stops
and the display remains at 65.53.
The motor run times (the number of times the inverter run command
is set to on) are calculated and displayed.
1.000 indicates 1,000 times. When any number ranging from 0.001
to 9.999 is displayed, the display increases by 0.001 per startup, and
when any number from 10.00 to 65.53 is displayed, the display in-
creases by 0.01 every 10 startups. When the total number exceeds
65,535, the display will be reset to 0 and the count will start again.
Shows the total number of times RS485 communications error has
occurred after the power is turned on.
Once the number of errors exceeds 9.999, the display (count) re-
turns to 0.
Shows the latest error that has occurred with RS485 communica-
tions in hexadecimal format.
For the error contents, refer to the user's manual of RS485 commu-
nication (MEH448).
Shows the ROM version of the inverter as a 4-digit display.
Shows the ROM version of the keypad panel as a 4-digit display.
(For remote keypad only.)
3-24