Chapter 7 MAINTENANCE AND INSPECTION

Perform daily and periodic inspection to avoid trouble and keep reliable operation for a long time.
Take care of the following items during work.
• The electric charge in the DC bus capacitor may be being charged even after the power is
turned off. Therefore, it may take a long time until the DC link circuit voltage reaches a
safety potential. Do not open the control circuit terminal block cover within 5 minutes after
the power has been turned off. Then remove the control circuit and main circuit terminal
block covers. Check that the DC link circuit voltage between main circuit terminals P (+) and
N (-) does not exceed the safety voltage (+25 VDC) with a multimeter and start the
maintenance and inspection.
Electric shock may occur.
• Maintenance, inspection, and parts replacement should be made only by authorized
persons.
• Take off the watch, rings and other metallic matter before starting work.
• Use insulated tools.
• Never remodel.
Electric shock or injuries could occur.

7.1 Daily Inspection

Visually inspect errors in the state of operation from the outside without removing the covers while
the inverter operates or while it is turned on.
-
Check if the expected performance (satisfying the standard specification) is obtained.
-
Check if the surrounding environment satisfies Chapter 2, Section 2.1 "Operating
Environment."
-
Check that the LED monitor displays normally.
-
Check for abnormal noise, odor, or excessive vibration.
-
Check for traces of overheat, discoloration and other defects.