2 – Ignore AC Fail
If this option is selected, the MAINS indicator does
not flash and the codepad does not beep every
minute when the AC MAINS is disconnected from
the control panel. If you want a programmable
output to operate when the AC MAINS fails, use
Output Event Type 1,4 AC Fail (refer to page 72).
If this option is selected, an AC Loss report (Contact
ID Event Code 301) still reports to the base station
receiver unless Locations 416 and 417 are
programmed as 0 (refer to Section 15.22 System Status
– AC Fail Report on page 68).
4 – Zone Pulse Count Handover
If this option is selected, any zone pulse count
readings are handed over and accumulate to any
zone that is activated during the same arming cycle.
Zone pulse count handover only operates with zone
pulse count options 8 to 15. Refer to Section 14.3.3
Zone Pulse Count on page 61 and Section 14.3.4 Zone
Pulse Count Time on page 61 for more information.
24-Hour Zones can receive any handover
pulses from other zones. 24-Hour Zones
cannot hand over pulses to other zones.
8 – Handover Delay To Be Sequential
If this option is selected, handover delay is sequential
(that is, in numerical order from lowest to highest). If
the sequence is broken before the Entry Time
expires, an alarm occurs. If this option is not selected,
handover delay follows the entry path if a Delay
Zone is activated first. Refer to Section 14.3.2 Zone
Types on page 61 for more information about
Handover Zones.
18.4

System Options 4

495
Location
Default
0
1
Panel to power up disarmed (if power reset)
2
Arm/disarm tracking on power up
4
Internal crystal to keep time
8
Night arm station or RE005 installed
1 – Panel To Power Up Disarmed
If this option is selected, the control panel powers up
in the disarmed state when the battery and AC
MAINS are reconnected after the system is powered
down.
If this option is not selected, the system is always
powered up armed in AWAY Mode.
2 – Arm/Disarm Tracking on Power Up
If selected, the control panel keeps its current armed
status in non-volatile memory. If the control panel is
restarted due to a power failure, the control panel
returns to being armed or disarmed as it was before
the power failed.
Bosch Security Systems, Inc. | 12/08 | F01U089457-02
System and Consumer Options
Example
If the system is disarmed when the system is powered
down, the system returns to the disarmed state when
the system is powered back up.
4 – Internal Crystal To Keep Time
If this option is selected, the control panel uses the
internal crystal (XTAL) to keep track of time. This
option is useful in countries that do not have a
constant MAINS frequency. If this option is not
selected, the control panel uses the MAINS
frequency as a time base to keep time.
8 – Night Arm Station, or RE005 Installed
Select this option to use the RE005 2-Channel Radio
Interface or the CP105 Night Arm Station. This
option enables any of these three accessories to
operate the control panel. User Code 16 is used to
send Open/Close Reports when you use any of these
accessories.
The Night Arm Station cannot operate a
partitioned ICP-CC488 Control Panel.
18.5

Consumer Options 1

496
Location
Default
0
1
Test reports only when armed
2
Test report after siren reset
4
Auto arm in STAY Mode 1
8
STAY indicator to display Day Alarm status
1 – Test Reports Only When Armed
If this option is selected, Test Reports (Contact ID
Event Code 602) are only sent when the system is
armed. It is no longer necessary to send a Test
Report with an Opening and Closing Report every
day.
Most commercial premises are open during the
working week, so a Test Report is not necessary
because Open and Close Reports are sent at the
programmed time. If you want to manually send a
Test Report, press and hold [9] button until two
beeps sound.
Refer to Section 15.28 Test Reporting Time to set the
desired Test Report time. To set the first Test Report,
refer to Section 5.1.2 Set the Number of Days until the
First Test Report.
2 – Test Report after Siren Reset
Select this option to force the control panel to send a
Test Report after the siren is reset. This can be used
to indicate to the monitoring station that the control
panel itself was not tampered with during the alarm
period.
4 – Auto Arm in STAY Mode 1
Select this option if automatic arming in STAY Mode
1 is preferred to automatic arming in AWAY Mode.