2,7
Fire Alarm Verification
This feature is used on some commercial fire control
panels to reduce false alarms from smoke detectors.
It is similar to zone pulse count used in some motion
detectors. A fire zone is allotted a pulse count of 3
pulses over a period of 3 min.
If the smoke detector trips, the voltage to the smoke
detector is disconnected for 15 sec and then
reapplied. No alarm is registered.
If the unit activates again within 3 min of the first
activation, no alarm is registered and the voltage to
the smoke detector is again disconnected for 15 sec
and then reapplied.
If a third activation is detected within 3 min of the
first activation, (three pulses in 3 min) a fire alarm is
registered. Power to the smoke detector is maintained
to facilitate unit identification through the detector
memory.
Connect this output to the negative side of any
fire/smoke detector. To configure an output for this
feature, use these settings.
EVENT TYPE – 2,7
POLARITY – 10
TIMEBASE – 2
MULTIPLIER – 15
The zone to which the fire or smoke detector is
connected should be programmed as:
ZONE TYPE – 13
ZONE PULSE COUNT – 3
ZONE PULSE COUNT TIME – 15
2,8
Remote Control 1
2,9
Remote Control 2
2,10
Remote Control 3
These outputs can be remotely activated (turned on
or off) by the following methods:
Remote codepad (refer to Section 5.2.7 Turning
Outputs On/Off for more information).
Remotely through the Alarm Link Software
(refer to your Alarm Link Instruction Manual for
further information).
2,11
Radio Control Output 1
This output operates when the [DOOR] button on
the 4-channel hand-held transmitter is activated when
the system is armed or disarmed.
2,12
Radio Control Output 2
This output operates when the [AUX] button on the
4-channel hand-held transmitter is activated when the
system is armed or disarmed.
If you select Option 8 in Location 492 (refer to
Section 18.1 System Options 1 on page 80), this output
does not operate and arms the system in STAY
Mode 1 only.
Bosch Security Systems, Inc. | 12/08 | F01U089457-02
Programmable Outputs
2,13
Radio Control Output 1 – Not in AWAY
Mode
This output operates when the [DOOR] button on
the 4-channel hand-held transmitter is activated when
the system is disarmed or armed in STAY Mode 1 or
STAY Mode 2. The output does not operate when
the system is armed in AWAY Mode.
2,14
Radio Control Output 2 – Not in AWAY
Mode
This output operates when the [AUX] button on the
4-channel hand-held transmitter is activated when the
system is disarmed or armed in STAY Mode 1 or
STAY Mode 2. The output does not operate when
the system is armed in AWAY Mode.
If you select Option 8 in Location 492 (refer to
Section 18.1 System Options 1 on page 80), this output
does not operate and arms the system in STAY
Mode 1 only.
2,15
Communications Failure after Three
Unsuccessful Calls
This output operates after the communication dialer
makes three unsuccessful calls to the base station
receiver. The output is reset when all messages are
transmitted (that is, when the buffer is empty or when
all possible attempts are made).
3,0
Communications Failure
This output operates after the communication dialer
makes all possible attempts to reach the base station
receiver. The output is reset when the first Kiss-Off is
received. This output does not operate for domestic
formats.
3,1
Dialer Disabled
This output operates when the Dialer reporting
functions allowed option (1) in Location 177 is not
selected (refer to Section 12.1 Dialer Options 1 on page
52). The output is reset when Option 1 is selected.
3,2
Dialer Active
This output operates when the communication dialer
is online. The output is reset when the
communication dialer releases the telephone line.
3,3
Ring Detect
This output operates when an incoming call is
detected by the control panel. The output is reset
when the ringing stops or when the call is answered.
3,4
Codepad Panic (Multi-Break)
This output operates when a Panic Alarm is initiated
from the codepad. The output operates for 200 ms if
the polarity is programmed as 1. You can program
the time base and multiplier to increase the period
during which the output operates.