ICP-CC488 | Installation Guide | 14.0
13 – 24-Hour Fire Zone
A 24-Hour Fire Zone (Contact ID Event Code 110) is
always ready to activate the dialer, horn speaker,
bell, and strobe, whether the system is armed or
disarmed. A distinct fire sound is emitted through the
horn speaker to indicate this type of alarm. This fire
sound is completely different from the burglary
sound. A 24-Hour Fire zone does not send a Restore
Report until the zone is restored.
14 – Chime Zone
A Chime Zone is not a burglary zone. It can never
sound the sirens or activate the dialer. Its purpose is
to map the zone to a programmable output to
indicate if the zone is sealed or unsealed. Refer to
Output Event Type 4,5 Global Chime on page 75.
Chime zones require EOL resistors and are
registered at a remote codepad. These zones do not
affect the operation of forced arming.
15 –Zone Not Used
If a zone is not used, program the zone type location
to 15. An EOL resistor is not required if this zone
type is used. This zone type never sounds the sirens
or activates the dialer.
14.3.3

Zone Pulse Count

Zone pulse count is the number of times a zone must
be activated before the zone registers an alarm. The
number can vary from 0 to 15. The zone pulse count
value is relative to the time frame (that is, the number
of pulses that must be present during a particular
time frame). Refer to Section 14.3.4 Zone Pulse Count
Time for time frame settings.
A zone that is programmed with a pulse
count activates an alarm when it is
continuously unsealed for 10 sec. A 24-
Hour Fire Zone programmed with a pulse
count activates an alarm when it is
continuously unsealed for 30 sec.
Zone Pulse Count Handover
Zone pulse count handover operates only with Zone
Pulse Count Time options 8 to 15. Refer to Section
14.3.4 Zone Pulse Count Time for more information.
Any zone that registers one activate pulse
automatically increments any other zone pulse count
that already registered at least one activate pulse
during its respective time. To enable this feature,
select Option 4 in Location 494 (refer to Section 18.3
System Options 3 on page 81).
24-Hour Zones will receive all handover
pulses from other zones. 24-Hour Zones
cannot handover pulses to other zones.
Bosch Security Systems, Inc. | 12/08 | F01U089457-02
Zone Information
14.3.4

Zone Pulse Count Time

Zone pulse count time is the time frame or period
over which the programmed number of pulses must
register to activate an alarm.

Table 49: Zone Pulse Count Times

20 ms Loop Response
Option
Time (sec)
0
0.5
1
1
2
2
3
3
4
4
5
5
6
10
7
15
For zone pulse count time, options 0 to 7 have a zone
loop response time of 20 ms and options 8 to 15 have
a zone loop response time of 150 ms. Loop response
time is the length of time a zone must be unsealed
before it can register as a valid pulse.
Inertia sensors should use options 0 to 7 and PIR
detectors should use options 8 to 15.
24-Hour Zones can receive any handover
pulses from other zones. 24-Hour Zones
cannot hand over pulses to other zones.
14.3.5

Zone Options 1

This location has four programming options. You can
select any combination of the options by
programming a single value. Calculate this value by
adding the option bit numbers together. Refer to
Section 7.3 Programming Option Bits on page 36 for
more information.

Table 50: Zone Options 1

Option
Description
1
Lockout siren/lockout dialer
2
Delay Alarm reporting
4
Silent Alarm
8
Sensor watch
1 – Lockout Siren and Lockout Dialer
Lockout refers to one activation per arming cycle
(that is, a zone programmed for Lockout can activate
the sirens or dialer only once).
The next time the system is armed, the zone can
activate the sirens and dialer once more. Restore
signals are sent when the system is disarmed.
EN | 61
150 ms Loop Response
Option
Time (sec)
8
20
9
30
10
40
11
50
12
60
13
90
14
120
15
200