Figure 3-15 Hot-Swappable Power Supply Fan (Unit 2)
CAUTION:
follow ESD safety precautions can result in damage to the server.
NOTE:
A hot-swappable device does not require interaction with the operating system before
the device is removed from or installed into the server.
The ac power to the server does not need to be off to remove or replace a hot-swappable chassis
fan unit.

Removing a Hot-Swappable Fan Unit

To remove an I/O or power supply fan unit, follow these steps:
1.
If rack-mounted, slide the server out from the rack until it stops. (See
from the Rack" (page
2.
Remove the top cover. (See
68
Installing the System
Observe all ESD safety precautions before attempting this procedure. Failure to
58).)
"Removing the Top Cover" (page
"Extend the Server
65).)