Pluggable SATA Drive

2.5-inch Pluggable SATA HDD

The sever supports up to four 2.5-inch pluggable SATA HDDs, two on each server board
module. Four HDDs share the same removal and installation procedure. For your
reference, this section provides the steps of removing and installing one 2.5-inch
pluggable SATA HDD as an example.
Figure 33 shows the location of the 2.5-inch pluggable SATA HDD on the server chassis:
Note: Before you remove or install the pluggable HDD, complete the following steps:
1. Make sure the server is not turned on or connected to the AC power. To power off
the server, see
2. Disconnect all necessary cable connections.
3. Remove the HDD blank if the HDD blank is installed.

Removing a 2.5-inch Pluggable SATA HDD

1. Turn the lock counter-clockwise.
2. Slide the locking latch along the direction of the arrow.
3. The HDD carrier locking lever springs open by itself.
30

Figure 33. 2.5-inch Pluggable SATA HDD Location

"Power
Off".
®
Intel
Server System SR1680MV Service Guide