Summary of Contents for Intel SR1690WB - Server System - 0 MB RAM
Page 1
Intel® Server System SR1690WB Service Guide ® A Guide for Technically Qualified Assemblers of Intel Identified Subassemblies/ Products Intel Order Number E78186-004...
Page 2
Intel products are not designed, intended or authorized for use in any medical, life saving, or life sustaining applications or for any other application in which the failure of the Intel product could create a situation where personal injury or death may occur.
This document provides a brief overview of the features of the board/chassis, a list of accessories or other components you may need, troubleshooting ® information, and instructions on how to add and replace components on the Intel Server System SR1690WB. For the latest version of this manual, see http://support.intel.com/...
Product Contents ® ® The Intel Server System SR1690WB ships with the Intel Server Board S5500WB. For further information, see the following documents: ® • Intel Server Board S5500WB Technical Product Specification ® • Intel Server System SR1690WB Technical Product Specification The contents of the server system are listed below.
Page 5
• Operating system • For information about which accessories, memory, processors, and third-party hardware were tested and can be used with your board, and for ordering information for Intel products, see: http://support.intel.com/support/motherboards/server/ S5500WB/compat.htm ® Intel Server System SR1690WB Service Guide...
Page 6
® Intel Server System SR1690WB Service Guide...
Safety Information Important Safety Instructions Read all caution and safety statements in this document before performing any of the instructions. See also Intel Server Boards and Server Chassis Safety Information on the ® Intel Server Deployment Toolkit CD and/or at http://support.intel.com/support/...
Take care to grip with, but not squeeze, the pliers or other tool you use to remove a jumper, or you may bend or break the pins on the board. ® viii Intel Server System SR1690WB Service Guide...
Preface ........................iii About this Manual ......................... iii Manual Organization ......................iii Product Contents ........................iv ® Intel Server System SR1690WB - Product Contents ..........iv Safety Information ....................vii Important Safety Instructions ....................vii Wichtige Sicherheitshinweise ....................vii Consignes de sécurité ......................vii Instrucciones de seguridad importantes ................
Page 10
Removing the I/O Expansion Module(s) ..............49 ® ® Installing and Removing the Intel Remote Management Module 3 and the Intel RMM 3 NIC Installing the Intel® RMM3 and Intel® RMM3 NIC ............50 ® ® Removing the Intel RMM3 and Intel RMM3 NIC ............. 51 Replacing the Backplane Board ..................
Page 11
650-W Single Power Supply Input Voltages ................67 650-W Single Power Supply Output Voltages ..............67 System Environmental Specifications ..................68 ® Appendix B: Intel Server Issue Report Form ............69 Appendix C: LED Decoder ..................73 Appendix D: Getting Help ..................83 Warranty Information ......................83...
Page 12
Regulated Specified Components ................99 End-of-Life / Product Recycling ................. 100 Appendix F: Warranty .....................101 ® Limited Warranty for Intel Chassis Subassembly Products ..........101 Extent of Limited Warranty ..................101 Limitations of Liability ....................102 How to Obtain Warranty Service ................102 Appendix G: Installation/Assembly Safety Instructions ........105...
Page 13
Advertencias de alimentacién y eléctricas ..............126 Advertencias sobre el cable de alimentación ............126 Advertencias el acceso al sistema ................127 Advertencias sobre el montaje en bastidor ...............128 Descarga electrostática (ESD) ..................129 Otros riesgos ......................129 ® Intel Server System SR1690WB Service Guide xiii...
Page 14
® Intel Server System SR1690WB Service Guide...
Page 15
Figure 5. Configuration Jumper Location ................12 Figure 6. Light Guided Diagnostic LEDs ................. 14 Figure 7. Back Panel Connectors.................... 15 ® Figure 8. Front Control Panel - Intel Server System SR1690WB.......... 17 Figure 9. Server System I/O Connector Locations..............19 Figure 10. Optional Peripherals....................20 Figure 11.
Page 16
Figure 49. Installing the Rack Handle ..................60 Figure 50. Removing the Rack Handle ................... 60 Figure 51. CMOS Recovery Jumper..................65 Figure 52. Password Recovery Jumper.................. 66 Figure 53. Diagnostic LED Placement Diagram ..............73 ® Intel Server System SR1690WB Service Guide...
Page 17
List of Tables Table 1. Server System References ..................1 ® Table 2. Intel Server System SR1690WB Feature Summary ..........3 Table 3. NIC LED Descriptions ....................15 Table 4. Control Panel LED Functions ..................17 Table 5. List of Supported I/O Modules on SR1690WB ............24 Table 6.
Page 18
® xviii Intel Server System SR1690WB Service Guide...
Intel Server System SR1690WB Quick Start User's Guide in the product and need to product box install it Accessories or other Intel Spares and Configuration Guide can be found at: server products http://support.intel.com/support/motherboards/server/S5500WB/ Hardware (peripheral Tested Hardware and Operating System List can be found at: boards, adapter cards) http://support.intel.com/support/motherboards/server/S5500WB/...
Page 20
Firmware Update can be found at: updates http://support.intel.com/support/motherboards/server/S5500WB/ For diagnostics test Diagnostics: Platform Confidence Test (PCT) software Found at: http://support.intel.com/support/motherboards/server/S5500WB/ ® and available on the Intel Server Deployment Toolkit 3.0 CD that ships with your system. ® Intel Server System SR1690WB Service Guide...
Server System Features ® This chapter briefly describes the main features of the Intel Server System SR1690WB. This chapter provides illustrations of the product, a list of the server system features, and diagrams showing the location of important components and connections on the server system.
Processor 5600 series processors in FC-LGA 1366 Socket B package with up to 95 W Thermal Design Power (TDP). • Supports future processor compatibility guidelines ® 4.8 GT/s, 5.86 GT/s, and 6.4 GT/s Intel Quick Path Interconnect ® (Intel QPI).
Page 23
Matrox* G200 2D Video Graphics controller Uses 8 MB of the BMC 32 MB DDR2 Memory ® ® LAN Support Two 10/100/1000 ports provided by Intel 82576 with Intel Acceleration Technology (I/OAT) System Power Single 650-W power supply, 80 plus silver with PFC System Management On-board Server Engines* LLC Pilot II Controller.
Use caution to make sure no cables or wires are pinched and that the airflow from the fans is not blocked. Use the following figures to determine the correct cable routing for the SR1690WB system. ® Intel Server System SR1690WB Service Guide...
Power from BBU Power to Optical Drive to RAID Module Power to Backplane(2) IPMB Cable from Backplane SGPIO Cable from Backplane SATA Data Cables Server Board HDD 0 HDD 1 HDD 2 HDD 3 AF003307 ® Intel Server System SR1690WB Service Guide...
Hot swap backplane 650W power supply unit System Fans (CPU fans and Memory fans) J. Optional slimline optical drive Air Duct Hot swap HDD carrier PCI Express* add-in card bracket Figure 3. System Components ® Intel Server System SR1690WB Service Guide...
Slot 1 PCI Express* x8 Gen2 4-pin Fan Connector (MEM1) SGPIO Connector 4-pin Fan Connector (CPU1A) IMPB Connector 4-pin Fan Connector (CPU1) Serial Port B Processor Socket 1 Figure 4. Server Board Connector and Component Locations ® Intel Server System SR1690WB Service Guide...
ME BMC Update J7A2 DSR to DTR BMC Force Update J1B5 Normal Update Password Clear J1C2 Normal Clear Password BIOS Recovery Mode J1C3 Normal Recovery 5HVHW %,26 &RQÀJXUDWLRQ J1B4 Normal Reset BIOS &RQÀJXUDWLRQ AF003049 ® Intel Server System SR1690WB Service Guide...
® Intel Light Guided Diagnostics The server system contains numerous LEDs providing the following functions: • The System Status LED on the front and back panels (see Figure 6) shows the overall health of the system (green, blinking green, blinking amber, and off).
FLT_A2 FLT_B FLT_A1 FLT_C AF003216 Diagnostic LED CPU2 DIMM fault LEDs System Status LED System ID LED 5V Standby LED CPU1 DIMM fault LEDs Fan Fault LEDs Figure 6. Light Guided Diagnostic LEDs ® Intel Server System SR1690WB Service Guide...
No network connection NIC2 Solid Amber Network connection in place Blinking Amber Transmit/receive activity Right 10 Mbps connection (if left LED is on or blinking) Solid Amber 100 Mbps connection Solid Green 1000 Mbps connection ® Intel Server System SR1690WB Service Guide...
To enable RAID 5, this activation key is placed on the SATA Key connector that ® is located at the right side of the server board. For information on how to install the Intel RAID Activation Key AXXRAKSW5 accessory to enable RAID 5, see the documentation that is included with the accessory kit.
System NIC 2 Activity LED System Identification LED System Status LED System Identification Button USB 2.0 connectors – Port 0 & 1 ® Figure 8. Front Control Panel - Intel Server System SR1690WB Table 4. Control Panel LED Functions Color State Description...
Page 36
If the system is not powered down normally, it is possible the Power LED will blink at the same time the system status LED is off due to a failure or configuration change that prevents the BIOS from running. ® Intel Server System SR1690WB Service Guide...
Figure 9. Server System I/O Connector Locations Peripheral Devices The server system provides locations and hardware for installing hard drives and a slimline optical drive. You must purchase the drives separately. The following figure shows the available options. AF003221 ® Intel Server System SR1690WB Service Guide...
Server System SR1690WB can be mounted into a rack. Intel provides three options to mount this server into a rack. When installing the chassis into a rack, Intel recommends you install systems from the bottom of the rack to the top. In other words, install the first system in the rack into the bottom position of the rack, the second system in the second position from the bottom, and so on.
For a list of qualified components, see the links under “Server System References”. Processor ® ® ® The Intel Server System SR1690WB supports one or two Intel Xeon Processor 5500 ® ® series and Intel Xeon Processor 5600 series with 95W Thermal Design Power (TDP) or less and with a max data transfer rate of 6.4 GT/s.
DIMM timings (RAS latency, CAS latency, and so forth). Memory Sparing and Mirroring ® The spare mode is not supported by Intel Server System SR1690WB. With memory mirroring, the system maintains two copies of all data in the memory subsystem.
Intel RAID Activation Key ® If RAID 5 is needed, you can install the optional Intel RAID Activation Key AXXRAKSW5. To enable RAID 5, this activation key is placed on the SATA Key connector located at the left side of the server board. For information on how to install the ®...
AXX10GBIOMOD Dual-port 10 Gigabit Ethernet I/O Expansion Module with CX4 connectors. AXX4GBIOMOD2 Quad port Gigabit Ethernet I/O ® Expansion Module based on the Intel 82576EB Gigabit Ethernet Controller. AXXIBQDRMOD InfiniBand* I/O Expansion Module Single Port QDR. ® Intel Server System SR1690WB Service Guide...
Hardware Installations and Upgrades Before You Begin Before working with your server product, pay close attention to the “Safety Information” at the beginning of this manual. Note: Whenever you service the system, you must first power down the server and unplug all peripheral devices and the AC power cord.
Slide the cover forward (see letter “A” in Figure 14). 3. Tighten the screw at the rear of the server (see letter “B”) and install the two screws at the front of the server (see letter “C”). ® Intel Server System SR1690WB Service Guide...
2. Power down the server and unplug all peripheral devices and the AC power cable. 3. Remove the server system cover. For instructions, see “Removing the System Cover”. 4. Lift the processor air duct from its location behind the two system blower fans. ® Intel Server System SR1690WB Service Guide...
4. Lower the air duct into place; align the air duct side walls to the corresponding slots on the bracket behind the four system blower fans and insert into position. Use caution not to pinch or disengage cables that may be near or under the air duct. ® Intel Server System SR1690WB Service Guide...
1. Observe the safety and ESD precautions at the beginning of this book. 2. Turn off all peripheral devices connected to the server. 3. Turn off the server. 4. Disconnect the AC power cord from the server. ® Intel Server System SR1690WB Service Guide...
5. Gently spread the retaining clips at each end of the socket. The DIMM lifts from the socket. 6. Holding the DIMM by the edges, lift it from the socket, and store it in an anti-static package. ® Intel Server System SR1690WB Service Guide...
5. Locate the processor socket and open the socket lever (see Figure 18). AF003228 Figure 18. Lifting the Load Lever 6. Open the load plate (see letter “A” in Figure 18 and letter “B” in Figure 18). ® Intel Server System SR1690WB Service Guide...
Figure 19. Open the Load Plate 7. Remove the socket protective cover (see Figure 19). 8. Take the processor out of the box and remove the protective shipping cover (Figure 20). AF003292 Figure 20. Removing the socket ® Intel Server System SR1690WB Service Guide...
Figure 22. Close the Load Plate and Socket Lever Note: Make sure the alignment triangle mark and the alignment triangle cutout align correctly. To assist in package orientation and alignment with the socket: ® Intel Server System SR1690WB Service Guide...
Replacing a Processor 1. Observe the safety and ESD precautions at the beginning of this book. 2. Turn off all peripheral devices connected to the server. Turn off the server. ® Intel Server System SR1690WB Service Guide...
Installing and Removing a Hot-swap Hard Drive ® You can install up to two fixed SATA drives in the Intel Server System SR16WB90 Service Guide. See “Server System References”...
6. Align the holes in the drive to the holes in the drive carrier and attach it to the carrier with the screws that were attached to the drive blank. AF003303 Figure 25. 2.5 HDD Installation ® Intel Server System SR1690WB Service Guide...
Do not push on the black drive carrier lever until the lever begins to close by itself. 8. When the black drive carrier lever begins to close by itself, push on it to lock the drive assembly into place. AF003305 Figure 27. Locking the drive assembly ® Intel Server System SR1690WB Service Guide...
To maintain proper system cooling, if you do not install a device at this location, you must install the provided filler blank. Installing a Slimline Optical Drive 1. Remove the slimline drive bay filler blank, if installed. ® Intel Server System SR1690WB Service Guide...
3. Screw the latch to the optical drive, and plug in the composed SATA/SATA Power cable, which is shipped in system package. AF003312 Figure 29. Attaching the Brackets to the Optical Drive 4. Lead the SATA/SATA Power cable through the optical drive bay before inserting the drive. ® Intel Server System SR1690WB Service Guide...
6. Connect the SATA cable connector to SATA port 4 or 5 on server board. 7. Connect the SATA power connector to P6 connector from system power supply. AF003314 Figure 30. Installing the Optical Drive into the Server System ® Intel Server System SR1690WB Service Guide...
1. Lower the riser assembly into place (see letter “A”). 2. Align the two hooks in the riser assembly with the matching slots at the back of the server system (see letter “B”). ® Intel Server System SR1690WB Service Guide...
PCI bracket shield to the rear of the chassis to remove the shield. Retain the screw. 2. Insert the PCI card edge connector in the slot on the PCI riser. ® Intel Server System SR1690WB Service Guide...
1. Remove the screw holding the add-in card in place (see letter “A”). 2. Remove the PCI add-in card from the riser card connector (see letter “B”). AF003325 Figure 34. Removing a PCI Card in a Riser Card ® Intel Server System SR1690WB Service Guide...
If a fan in the power supply fails, you must replace the power supply. Use the following steps to replace a system fan. Replacing the System Fans 1. Remove the processor air duct. For instructions, see “Removing the Processor Air Duct”. ® Intel Server System SR1690WB Service Guide...
2. Disconnect the two 4-pin or one 8-pin system fan cables from the server board. See letters “2” in the following figure. 3. Lift the failed fan from the module. 4. Remove the plastic screws from the failed fans and install them into the new fans. ® Intel Server System SR1690WB Service Guide...
6. With the fan oriented correctly, insert the fan into the fan module (see letter “3”), and insert the fan cable into the matching connector on the server board. (see letter “2”). ® Intel Server System SR1690WB Service Guide...
Installing and Removing the I/O Expansion Module(s) Installing the I/O Expansion Module(s) 1. Squeeze the sides of the I/O expansion module cover to disengage it from the server system back panel and remove it (see letter “A”). ® Intel Server System SR1690WB Service Guide...
2. Attach the standoffs to the server board (see letter “A”) and attach the I/O shield gasket to the module (see letter “B”). 3. Attach the I/O expansion module(s) to the server board (see letter “C”). ® Intel Server System SR1690WB Service Guide...
1. Remove the I/O expansion module(s) from the server board (see letter “A”). 2. Remove the standoffs from the server board (see letter “B”). 3. Install the I/O expansion module cover into the system back panel (see letter “C”). ® Intel Server System SR1690WB Service Guide...
Remote ® Management Module 3 and the Intel RMM 3 NIC Installing the Intel® RMM3 and Intel® RMM3 NIC ® 1. Squeeze the sides of the Intel RMM3 NIC module cover to disengage it from the server system back panel and remove it (see letter “A”) AF003315 ®...
RMM3 NIC ® Use the reverse steps to remove the Intel RMM3 module ® 1. Remove the two screws from rear chassis to loosen Intel RMM3 board (see letter “C”). ® 2. Plug out Intel RMM3 NIC module cable from the server board (see letter “B”).
2. Tighten two screws to lock the backplane assembly in position (see letter “B”). 3. Connect data/power cables to the backplane connectors. 4. Engage hard drives back to the backplane (see letter “C”). ® Intel Server System SR1690WB Service Guide...
4. If installed, disconnect all SATA cables from the server board. 5. Disconnect the system fans cables from server board. 6. Disconnect all power cables coming from the power supply to the server board. ® Intel Server System SR1690WB Service Guide...
Installing the Server Board 1. Place the server board into the server system as shown in the following figure (see letter “A”). 2. Attach the server board with nine screws (see letter “B”). ® Intel Server System SR1690WB Service Guide...
4. Re-connect the system fan cables to server board. 5. Re-connect all SATA cables to the server board. 6. Install the PCI riser assembly. 7. Install the memory, processor heat sinks, and processors. 8. Install the system air duct. ® Intel Server System SR1690WB Service Guide...
Varning: Explosionsfara vid felaktigt batteribyte. Använd samma batterityp eller en ekvivalent typ som rekommenderas av apparattillverkaren. Kassera använt batteri enligt fabrikantens instruktion. Varoitus: Paristo voi räjähtää, jos se on virheellisesti asennettu. Vaihda paristo ainoastaan laitevalmistajan suosittelemaan tyyppiin. Hävitä käytetty paristo valmistajan ohjeiden mukaisesti. ® Intel Server System SR1690WB Service Guide...
Removing the Power Supply You can replace the power supply if it fails or if one of the fans integrated into it fails. To replace the power supply, use the following instructions. ® Intel Server System SR1690WB Service Guide...
3. Lift the power supply up to clear the chassis tab (see letter “C”) and remove the power supply by sliding it out (see letter “D”). Installing the Power Supply 1. Insert the replacement power supply by first engaging the back panel (see letter “A”). ® Intel Server System SR1690WB Service Guide...
Installing and Removing the Rack Handles Installing the Rack Handles 1. Align the rack handle with the holes on the side of the server system and attach the rack handle with the three screws. ® Intel Server System SR1690WB Service Guide...
2. Repeat step 1 on the opposite side of the server. Removing the Rack Handles 1. Remove the three screws holding the rack handle in place, and remove the rack handle from the server system. AF003327 Figure 50. Removing the Rack Handle ® Intel Server System SR1690WB Service Guide...
You can run the BIOS Setup with or without an operating system ® being present. See “Server System References” for a link to the Intel Server Board S5500WB Technical Product Specification where you can find details about specific BIOS setup screens.
If “No” is selected and the <Enter> key is pressed, or if <Esc> is pressed, the user is returned to where they were before <F9> was pressed without affecting any existing field values. ® Intel Server System SR1690WB Service Guide...
Press <F2> Key if you want to run SETUP 2. Write down the current settings in the BIOS Setup program. Note: Do not skip step 2. You need these settings to configure your server at the end of the procedure. ® Intel Server System SR1690WB Service Guide...
1. Power down the system; do not disconnect the AC power. 2. Open the server. 3. Move the jumper from the normal operation position, at pins 1 and 2 to the CMOS Clear Force Erase position, covering pins 2 and 3. ® Intel Server System SR1690WB Service Guide...
2. Open the server chassis. 3. Move the jumper from the normal operation position, Password Clear Protect, at pins 1 and 2 to the Password Clear Erase position, covering pins 2 and 3. ® Intel Server System SR1690WB Service Guide...
7. The password is now cleared and you can reset it by going into the BIOS setup. CMOS Clear J1B4 1-2: Default 2-3: Clear CMOS BMC Force Update J1B5 1-2: Default 2-3: Enabled Password Clear J1C2 1-2: Default 2-3: Password Clear AF003214 Figure 52. Password Recovery Jumper ® Intel Server System SR1690WB Service Guide...
Appendix A: Technical Reference 650-W Single Power Supply Input Voltages • 100-127V at 47/63 Hz; 8.6 A max. • 200-240V at 47/63 Hz; 4.3 A max. 650-W Single Power Supply Output Voltages The following table lists the total wattage available from the power subsystem for each voltage.
(23 +/- 2 degrees C). Electrostatic +/-12 kV except I/O port +/-8 KV, per Intel Environmental Test Specification. discharge (ESD)* *The system requires the use of a shielded LAN cable to comply with Immunity regulatory requirements.
Date Submitted: _______________________________________________________ Company Name: ______________________________________________________ Contact Name: ________________________________________________________ Email Address: _______________________________________________________ Intel Server Product: ___________________________________________________ Priority (Critical, Hot, High, Low): _______________________________________ Brief Problem Description. Provide a brief description below. See the last page for space to include a detailed problem description.
DIMM D2 MB and Vendor / part number: __________________________________ DIMM E1 MB and Vendor / part number: __________________________________ DIMM F1 MB and Vendor / part number: __________________________________ Operating System Information Operating System:_____________________________________________________ Version: _____________________________________________________________ Service Pack:_________________________________________________________ ® Intel Server System SR1690WB Service Guide...
Page 89
Description Revision Revision Address PCI Express* Gen2 x8 On-board Video Add-in Video On-board NIC1 (10/ 100/1000Mb/s) On-board NIC2 (10/ 100/1000Mb/s) ® Intel Expansion Module Revision #NIC Hard Drive Information Drive Type (SATA/ Make/Model Revision SAS) SATA_0 SATA_1 SATA_2 SATA_3 SATA_4...
Page 90
Please also include any details on troubleshooting already done. ____________________________________________________________________ ____________________________________________________________________ ____________________________________________________________________ ____________________________________________________________________ ____________________________________________________________________ ____________________________________________________________________ ____________________________________________________________________ ____________________________________________________________________ ____________________________________________________________________ ____________________________________________________________________ ____________________________________________________________________ ____________________________________________________________________ ____________________________________________________________________ ____________________________________________________________________ ____________________________________________________________________ ____________________________________________________________________ ____________________________________________________________________ ____________________________________________________________________ ____________________________________________________________________ ____________________________________________________________________ ____________________________________________________________________ ® Intel Server System SR1690WB Service Guide...
Appendix C: LED Decoder During the system boot process, the BIOS executes a number of platform configuration processes, each of which is assigned a specific hex POST code number. As each configuration routine is started, the BIOS displays the POST code to the POST Code Diagnostic LEDs on the back edge of the server board.
SMM initialization 0x14h Selection of Processor with least feature use as Boot Strap Processor 0x15h Switch an AP processor to become the new Boot Strap Processor Chipset 0x21h Initializing a chipset component Memory ® Intel Server System SR1690WB Service Guide...
Page 93
(system halted) 0xEBh Memory test failed (system halted) 0xECh Unsupported or invalid DIMM configuration (system halted) 0xEDh Unsupported or invalid DIMM configuration (system halted) 0xEBh DIMM with corrupted SPD data detected (system halted) ® Intel Server System SR1690WB Service Guide...
Page 95
Memory Initialization of Integrated Memory Controller 0xBCh Memory Initialization of Integrated Memory Controller 0xBDh Memory Initialization of Integrated Memory Controller 0xBEh Memory Initialization of Integrated Memory Controller 0xBFh Memory Initialization of Integrated Memory Controller ® Intel Server System SR1690WB Service Guide...
Page 96
0x5Bh Reserved for ATA SMBUS 0x5Eh Resetting SMBUS 0x5Fh Reserved for SMBUS I/O Controller Hub 0x61h Initializing I/O Controller Super I/O 0x63h Initializing Super I/O Local Console 0x70h Resetting the video controller (VGA) ® Intel Server System SR1690WB Service Guide...
Page 97
Detecting the presence of mouse 0x9Bh Enabling the mouse 0x9Ch Reserved for mouse Serial Port 0xA8h Resetting the serial port 0xA9h Disabling the serial port 0xAAh Detecting the presence of the serial port ® Intel Server System SR1690WB Service Guide...
Page 98
0xD0 Entered the Boot Device Selection phase (BDS) 0xD1 Return to last good boot device 0xD2 Set up boot device selection policy 0xD3 Connect boot device controller 0xD4 Attempt flash update boot mode ® Intel Server System SR1690WB Service Guide...
Page 99
Started dispatching drivers 0xE6h Started connecting drivers DXE Drivers 0xE7h Waiting for user input 0xE8h Checking password 0xE9h Entering BIOS setup 0xEAh Flash Update 0xEBh Legacy Option ROM Initialization 0xECh DXE Drivers initialized ® Intel Server System SR1690WB Service Guide...
Page 100
Loading crisis recovery capsule 0x35h Handing off control to the crisis recovery capsule 0x36h Begin crisis recovery 0x3Eh No crisis recovery capsule detected 0x3Fh Crisis recovery capsule failed integrity check of capsule descriptors ® Intel Server System SR1690WB Service Guide...
— A searchable knowledge base to search for product information throughout the support site 2. If you are still unable to obtain a solution to your issue, send an e-mail to Intel’s technical support center using the online form available at http://supportmail.intel.com/scripts-emf/welcome.aspx...
Page 102
® Intel Server System SR1690WB Service Guide...
(or higher) and operating at the same (or higher) speed as the microprocessor used on this server board. The final configuration of your end system product may require additional EMC compliance testing. For more information, please contact your local Intel representative.
Product EMC Compliance - Class A Compliance Note: Legally the product is required to comply with Class A emission requirements as it is intended for a commercial type market place. Intel targets 10db margin to Class A Limits ® The Intel...
Note: Certifications Emissions requirements are to Class A. Table 11. Product Regulatory Compliance References Compliance Compliance Compliance Reference Marking Regional Reference Example Description Australia / New AS/NZS CISPR22 (Emissions) Zealand N232 Argentina IRAM Certification (Safety) ® Intel Server System SR1690WB Service Guide...
Page 106
EMC Directive 2004/108/EEC EN55022 (Emissions) EN55024 (Immunity) EN61000-3-2 (Harmonics) EN61000-3-3 (Voltage Flicker) CE Declaration of Conformity Germany GS Certification – EN60950-1 International CB Certification – IEC60950-1 None Required CISPR 22 / CISPR 24 Japan VCCI Certification ® Intel Server System SR1690WB Service Guide...
Page 107
Compliance Reference Marking Regional Reference Example Description Korea KCC Certification 인증번호: CPU-SR1690(A) Russia GOST-R 50377-92 Certification GOST R 29216-91 (Emissions) GOST R 50628-95 (Immunity) MO04 Ukraine Certification Ukraine None Required BSMI CNS13438 Taiwan R33025 ® Intel Server System SR1690WB Service Guide...
(1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. For questions related to the EMC performance of this product, contact: Intel Corporation 5200 N.E. Elam Young Parkway Hillsboro, OR 97124-6497 1-800-628-8686 This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules.
Interference (VCCI) from Information Technology Equipment. If this is used near a radio or television receiver in a domestic environment, it may cause radio interference. Install and use the equipment according to the instruction manual. ® Intel Server System SR1690WB Service Guide...
(pedestal orientation) or side (rack mount configuration). The BSMI Certification Marking and EMC warning is located on the outside rear area of the product. KCC (Korea) Following is the KCC certification information for Korea. 인증번호 : CPU-SR1690 (A) ® Intel Server System SR1690WB Service Guide...
Location in accordance with articles 110-16, 110-17, and 110-18 of the National Electric Code, ANSI/NFPA 70. The DC source must be electrically isolated by double or reinforced insulation from any hazardous AC source. ® Intel Server System SR1690WB Service Guide...
Connector, server end: The connectors that plug into the AC receptacle on the server must be an approved IEC (International Electrotechnical Commission) 320, sheet C13, type female connector. • Cord length and flexibility: Cords must be less than 4.5 meters (14.76 feet) long. ® Intel Server System SR1690WB Service Guide...
Product Ecology Compliance Intel has a system in place to restrict the use of banned substances in accordance with world wide product ecology regulatory requirements. The following is Intel's product ecology compliance criteria. Table 12. Product Ecology Compliance Compliance Regional...
Page 114
Polybrominated Biphenyls Diphenyl Ethers (PBB/PBDE) • Quantity limit of 0.01% by mass (100 PPM) for: Cadmium Intel Internal Specification All materials, parts and None Required subassemblies must not contain restricted materials as defined in Intel’s Environmental Product Content Specification of Suppliers and Outsourced Manufacturers –...
Page 115
Table 12. Product Ecology Compliance Compliance Regional Compliance Reference Marking Compliance Reference Description Example Recycling Markings – Fiberboard (FB) and Cardboard (CB) are marked with international recycling marks. Applied to outer bulk packaging and single package. ® Intel Server System SR1690WB Service Guide...
为避免遭受电击, 在进行维修之前应断开两 (2)条电源系统电缆。 Traditional Chinese: 注意: 本設備包括多條電源系統電纜。 為避免遭受電擊, 在進行維修之前應斷開兩 (2)條電源系統電纜。 German: Dieses Geräte hat mehr als ein Stromkabel. Um eine Gefahr des elektrischen Schlages zu verringern trennen sie beide (2) Stromkabeln bevor Instandhaltung. ® Intel Server System SR1690WB Service Guide...
Updated product information for configurations can be found on the Intel Server Builder Web site at the following URL: http://channel.intel.com/go/serverbuilder If you do not have access to Intel's Web address, please contact your local Intel representative. • Server Chassis: (base chassis is provided with power supply and fans) - NRTL listed.
End-of-Life / Product Recycling Product recycling and end-of-life take-back systems and requirements vary by country. Contact the retailer or distributor of this product for information about product recycling and / or take-back. ® Intel Server System SR1690WB Service Guide...
“as is” unless specifically provided for otherwise in any software license accompanying the software. If any Product furnished by Intel which is the subject of this Limited Warranty fails during the warranty period for reasons covered by this Limited Warranty, Intel, at its option, will: •...
Limitations of Liability Intel's responsibility under this, or any other warranty, implied or expressed, is limited to repair, replacement, or refund, as set forth above. These remedies are the sole and exclusive remedies for any breach of warranty.
Telephone Support If you cannot find the information you need on Intel's World Wide Web site (http:// www.intel.com/), call your local distributor or an Intel Customer Support representative.
Page 122
® Intel Server System SR1690WB Service Guide...
Appendix G: Installation/Assembly Safety Instructions Important Safety Instructions Read all caution and safety statements in this document before performing any of the instructions. See also Intel Server Boards and Server Chassis Safety Information on the Resource CD and/or at: http://support.intel.com/support/motherboards/server/sb/cs-010770.htm English...
Wichtige Sicherheitshinweise Lesen Sie zunächst sämtliche Warn- und Sicherheitshinweise in diesem Dokument, bevor Sie eine der Anweisungen ausführen. Beachten Sie hierzu auch die Sicherheitshinweise zu Intel-Serverplatinen und -Servergehäusen auf der Ressourcen-CD oder unter: http://support.intel.com/support/motherboards/server/sb/cs-010770.htm SICHERHEISMASSNAHMEN: Immer wenn Sie die Gehäuseabdeckung abnehmen um an das Systeminnere zu gelangen, sollten Sie folgende Schritte beachten: 1.
Lisez attention toutes les consignes de sécurité et les mises en garde indiquées dans ce document avant de suivre toute instruction. Consultez Intel Server Boards and Server Chassis Safety Information sur le CD Resource CD ou bien rendez-vous sur le site: http://support.intel.com/support/motherboards/server/sb/cs-010770.htm...
Page 126
Instrucciones de seguridad importantes Lea todas las declaraciones de seguridad y precaución de este documento antes de realizar cualquiera de las instrucciones. Vea Intel Server Boards and Server Chassis Safety Information en el CD Resource y/o en: http://support.intel.com/support/motherboards/server/sb/cs-010770.htm INSTRUCCIONES DE SEGURIDAD: Cuando extraiga la tapa del...
Se il sistema è stato a lungo in funzione, il microprocessore e il dissipatore di calore potrebbero essere surriscaldati. Fare attenzione alla presenza di piedini appuntiti e parti taglienti sulle schede e sul telaio. È consigliabile l'uso di guanti di protezione. ® Intel Server System SR1690WB Service Guide...
Page 128
® Intel Server System SR1690WB Service Guide...
To reduce the risk of bodily injury, electrical shock, fire, and equipment damage, read this document and observe all warnings and precautions in ® this guide before installing or maintaining your Intel Server Product. In the event of a conflict between the information in this document and information provided with the product or on the website for a particular product, the product documentation takes precedence.
Conform to local occupational health and safety requirements when moving and lifting equipment. • Use mechanical assistance or other suitable assistance when moving and lifting equipment. • To reduce the weight for easier handling, remove any easily detachable components. ® Intel Server System SR1690WB Service Guide...
Deutsch Sicherheitshinweise für den Server ® ® Das vorliegende Dokument bezieht sich auf Intel Serverplatinen, Intel Servergehäuse (Standfuß und Rack) sowie installierte Peripheriegeräte. Es enthält Warnungen und Vorsichtsmaßnahmen zur Vermeidung von Gefahren durch Verletzung, Stromschlag, Feuer und Beschädigungen von Geräten. Lesen Sie diese Dokument daher sorgfältig, ®...
Verwenden Sie mechanische oder andere geeignete Hilfsmittel zum Transportieren oder Anheben von Geräten. • Entfernen Sie alle Komponenten, die sich leicht abnehmen lassen, um das Gewicht zu reduzieren und die Handhabung zu erleichtern. ® Intel Server System SR1690WB Service Guide...
Typ entspricht. Jedes Netzteil im System muß über ein eigenes Netzkabel angeschlossen werden. Einige Netzteile von Intel Servern verwenden Nullleitersicherungen. Vorsicht ist geboten im Umgang mit Netzteilen, welche Nullleitersicherungen verwenden, um das Risiko eines elektrischen Schlages zu vermeiden Das Netzteil in diesem Produkt enthält keine Teile, die vom Benutzer gewartet werden...
Gehen Sie bei der Installation von Geräten im Rack immer von unten nach oben vor, und bauen Sie das schwerste Gerät an der untersten Position im Rack ein. Ziehen Sie jeweils immer nur ein Gerät aus dem Rack heraus. ® Intel Server System SR1690WB Service Guide...
Inbetriebnahme des Systems ohne Abdeckung kann zur Beschädigung von Systemkomponenten führen. So bringen Sie die Abdeckung wieder an: • Vergewissern Sie sich zunächst, daß Sie keine Werkzeuge oder Teile im Gehäuse vergessen haben. ® Intel Server System SR1690WB Service Guide...
® d’installer ou de mettre à jour votre produit serveur Intel En cas de conflit entre les informations fournies dans ce document et celles livrées avec le produit ou publiées sur le site Web pour un produit particulier, la documentation du produit prime.
Bien ventilé et à l’écart des sources de chaleur telles que la lumière directe du soleil et les radiateurs. • À l’écart des sources de vibration ou des chocs physiques. • Isolé des champs électromagnétiques importants produits par des appareils électriques. ® Intel Server System SR1690WB Service Guide...
Vous devez les débrancher avant d’ouvrir le châssis, d’ajouter ou de supprimer un composant non connectable à chaud. Les alimentations de certains serveurs Intel sont munies de doubles fusibles pôle/neutre: veuillez observer les précautions d'usage afin d'éviter tout risque d'eléctrocution.
Éteignez le système en appuyant sur le bouton d’alimentation. • Déconnectez l’alimentation secteur en débranchant tous les cordons d’alimentation secteur du système ou de la prise murale. • Déconnectez l’ensemble des câbles et lignes de télécommunication qui sont connectés au système. ® Intel Server System SR1690WB Service Guide...
étiqueté comme contrôlant toute l’unité, et pas uniquement le ou les serveurs. Pour éviter tout risque d’électrocution, le rack et chaque élément de l’équipement installé dans le rack doivent être correctement reliés à la terre. ® Intel Server System SR1690WB Service Guide...
Vérifiez tout d’abord que vous n’avez pas oublié d’outils ou de composants détachés à l’intérieur du système. • Vérifiez que les câbles, les cartes d’extension et les autres composants sont correctement installés. • Fixez les panneaux au châssis en suivant les instructions du produit. ® Intel Server System SR1690WB Service Guide...
Retournez-les au fabricant en cas de problème. Español Información de seguridad del servidor ® Este documento se aplica a las tarjetas de servidor de Intel , las carcasas de servidor de ® Intel (montaje en bastidor y en pedestal) y los dispositivos periféricos. Para reducir el riesgo de daños corporales, descargas eléctricas, fuego y en el equipo, lea este documento...
Provista de una toma de corriente alterna correctamente conectada a tierra. • Provista de espacio suficiente para acceder a los cables de la fuente de alimentación ya que constituyen la desconexión principal de la alimentación. ® Intel Server System SR1690WB Service Guide...
CA estén desenchufado antes de abrir la carcasa, agregar o extraer cualquier componente que no es de conexión en funcionamiento. Algunas fuentes de alimentación de electricidad de los servidores de Intel utilizan el polo neutral del fuselaje. Para evitar riesgos de choques electricos use precauciónes al trabajar con las fuentes de alimentación que utilizan el polo neutral de fuselaje.
Devuélvala al fabricante para repararla. • Apague el servidor y desconecte todos los cables de alimentación antes de agregar o reemplazar cualquier componente que no es de conexión en funcionamiento. ® Intel Server System SR1690WB Service Guide...
Para evitar el riesgo de descargas eléctricas, deberá instalar una conexión a tierra apropiada para el bastidor y para cada pieza del equipo instalada en el mismo. ® Intel Server System SR1690WB Service Guide...
Deseche las baterías respetando la normativa local. No intente recargar la batería. No intente desmontar, pinchar o causar cualquier otro desperfecto a una batería. ® Intel Server System SR1690WB Service Guide...
Page 148
Precaución Para evitar el riesgo de la exposición a radiaciones o de daños personales: • No abra la caja de ningún periférico o dispositivo láser • Los periféricos o dispositivos láser no pueden ser reparados por el usuario • Haga que el fabricante los repare ® Intel Server System SR1690WB Service Guide...