Toshiba GR200 Series Instruction Manual page 1355

Line differential protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

IP setting example [RedundantMode]=Hot_standby
(vii)
When Hot_standby is set for the setting [RedundantMode], the user can apply single IP
address in the IED. The table below shows that both Port A and B have the same IP address.
Table 11.2-4 Default IP address for Hot standby operation
Protocol
IEC61850(GOOSE)
IP address at
Port A†
192.168.1.11
IP address at
Port B†
†Note: Address '192.168.1.11' is set as default. Setting [IPADDRESS2] will be neglected.
IP setting example [RedundantMode]=Fixed
(viii)
If Fixed is set for the setting [RedundantMode], the user can apply IP addresses in the IED.
The table below shows that both Port A and B can have different IP addresses.
Table 11.2-5 Default IP address for Fix operation
Protocol
IEC61850(GOOSE)
IP address at
192.168.1.11
Port A†
IP address at
Not applicable
Port B
†Note: Port A '192.168.1.11 (default)' is ready for IEC61850 (GOOSE), but Port B is not
ready for IEC61850.
‡Note: Single IP address is generally set in SNTP. The user is not recommended to have
Time synchronization using different IP addresses with 'Port A' and 'Port B'.
§Note: For the local PC engineering, the use of Port B (192.168.1.12, default) is
recommended, but the user can also use Port A (192.168.1.11, default) for that.
SNTP
192.168.1.11
SNTP
192.168.1.11
192.168.1.12‡
- 1332 -
6F2S1914 (0.49)
GR-TIEMS® /
MULTIPLOG®
192.168.1.11
GR-TIEMS® /
MULTIPLOG®
192.168.1.11
192.168.1.12§
GRL200 (Soft 033 & 037)