Functional Data (1/7)
Phase-segregated Current Differential Protection
DIFI1 (Small current region)
DIFI2 (Large current region)
DIFL-Slope1 (Small current region)
DIFL-Slope2 (Large current region)
Time setting for DIF
Reference voltage
Operating time
Resetting time
Zero-sequence Current Differential Protection for high-resistance earth
DIFGI
DIFG-Slope
Timer
Operating time
Resetting time
Charging Current Compensation
DIFL-IcC
Differential Current Supervision
DIFSV
Timer
DIF Guard characteristic
Overcurrent threshold
Rate of Overcurrent change threshold
Phase sequence Undervoltage threshold
Phase to Phase Undervoltage threshold
Rate of voltage change threshold
DIFG Guard characteristic
Rate of Earth fault change threshold
0.10 to 2.00A in 0.01A steps (1A rating)
0.50 to 10.00A in 0.01A steps (5A rating)
0.6 to 60.0A in 0.1A steps (1A rating)
3.0 to 300.0A in 0.1A steps (5A rating)
10 to 50 %
50 to 100 %
0.00 to 100.00s in 0.01s steps
100 to 120V in 1V step
Less than 1 cycle at 300% of DIFI1
Less than 110 ms (for tripping output)
Less than 40 ms (for signal output)
0.05 to 1.00A in 0.01A steps (1A rating)
0.25 to 5.00A in 0.01A steps (5A rating)
10 to 50 %
0.00 to 300.00s in 0.01s steps
less than 45ms
less than 100ms
0.00 to 1.00A in 0.01A steps (1A rating)
0.00 to 5.00A in 0.01A steps (5A rating)
0.05 to 2.00A in 0.01A steps (1A rating)
0.25 to 10.00A in 0.01A steps (5A rating)
0 to 300s in 1s steps
0.02 to 50.00A in 0.01A steps (1A rating)
0.10 to 250.00A in 0.01A steps (5A rating)
0.05 to 0.20A in 0.01A steps (1A rating)
0.25 to 1.00A in 0.01A steps (5A rrating)
5.0 to 130.0V in 0.1V steps
5.0 to 130.0V in 0.1V steps
1 to 20V in 1steps
0.02 to 50.00A in 0.01A steps (1A rating)
0.10 to 250.00A in 0.01A steps (5A rating)