Figure 4.11-6 LN editing screen for SBO mode (for example)
Defining DIR mode
Figure 4.11-7exemplifies the settings in LN "GAPC1" when the DIR mode is required for the
ASEQ01 function. In the DIR mode, the following three items should be selected using the GR-
TIEMS software:
Figure 4.11-7 LN editing screen for DIR mode (for example)
Mapping output data
(ii)
The user should group the ASEQ01 signals with regard to GOOSE and REPORT; the user
should map them for IEC61850 communication using GR-TIEMS.
Table 4.11-11 shows the signals in the ASEQ01 function that require mapping to the IEC
61850 communications. Figure 4.11-8 shows how to map a signal.
SBOw
Oper
Cancel
Origin
stSeld
sboClass† (choice "operate-once")
ctlmodel (choice "SBOes or SBOns" )
†"sboClass" can be found by scrolling down
Oper
Origin
ctlmodel (choice "DOes or DOns")