Toshiba GR200 Series Instruction Manual page 1524

Line differential protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

Line protection IED
GRL200
-11-224-12-1J-30-120
5A
50 / 60
100-120
110-250
TOSHIBA ENERGY SYSTEMS & SOLUTIONS CORPORATION
Rated current (In) on the nameplate: 5A rated set in the Manufacture
Information
10:48
[IED TYPE]
Altered code
GRL200
-11-224-12-1J-30-110
__-1033-1J2-2E
[Serial No.]
No XXXXXXX123
Figure 13.4-1 How to check the changed rated current with the altered code
†Note: For the LCD screen operation, see
‡Note: To know how to read the code, refer to the preceding section
inspection of hardware and software
Step6: Write settings with altered code
To write the settings corresponding to the altered code, use the GR-TIEMS. For
example, after rated current changed to 1A, rewrite the setting items into the IED
using the altered ordering code (see Figure 13.4-1 about the altered code; in this
example: GRL200-11-224-12-1J-30-110-1033-1J2-2E). Figure 13.4-2 shows how to
write the settings.
Original code
Month, Year
****** ** ***
1/9
Code at
Positon K
1
2
Rated current (In) in the IED: 1A rated changed by the user
Chapter User interface: Information sub-menu
- 1501 -
Rated
current
1A
5A
.
6F2S1914 (0.49)
.
Unpack and
GRL200 (Soft 033 & 037)