No.
Phenomena
Time can be
not
synchronised
3
with IEC103
communicati
on.
†Note: BCU: Bay control unit, RY: Relay
‡Note: The user should set "even" for the parity setting. Not allowed to set except "even".
Supposed causes
BCU does not transmit the
time synchronisation frame.
The settling of the time
synchronisation source is set
to other than IEC.
Object†
Transmit the time synchronisation
BCU
Change the settling of time
synchronisation source to IEC.
RY
- 1644 -
6F2S1914 (0.49)
Check / Confirmation
Procedure
frame.
GRL200 (Soft 033 & 037)