Table 5.4-4 Setting items for binary input circuits in the variable type (i.e., BI2A module)
Setting devices
BI1-3_PICKUP
BI4-6_PICKUP
BI7-9_PICKUP
Common
BI10-12_PICKUP
CMP_NUM
BI1_CPL
BI1
On Delay Timer
Off Delay Timer
INVERSE-SW
BI2_CPL
BI2
On Delay Timer
Off Delay Timer
INVERSE-SW
BI3_CPL
BI3
On Delay Timer
Off Delay Timer
INVERSE-SW
.....
.....
BI
n
_CPL
n
BI
On Delay Timer
4
Off Delay Timer
INVERSE-SW
Note: BI1_CPL~BI12_CPL settings are provided for the BI2A module.
4
As an example, Figure 5.4-1 shows the binary input circuit of the BI1A in order to help
understand the settings. The BI1A consists of 18 binary input circuits and each circuit has
three settings:
Setting threshold level
Comparison feature for contact chatter
CPL switches ("Delayed pick-up and delayed drop-off signal" and "Logic level
inversion"), used as basis of input signal characteristics.
Range
18 to 222
V Guaranteed-minimum-pick-ups at BI1, BI2, and BI3
18 to 222
V Guaranteed-minimum-pick-ups at BI4, BI5, and BI6
18 to 222
V Guaranteed-minimum-pick-ups at BI7 to BI9
18 to 222
V Guaranteed-minimum-pick-ups at BI10 to BI12
4 to 9
Number of times in the filter
Off/On
Switch for programmable operation in BI1
0.000 to 300.000 s
Value in the on-delay timer
0.000 to 300.000 s
Value in the off-delay timer
Normal / Inverse –
Inversion operation of BI1 signal
Off/On
Switch for programmable operation in BI 2
0.000 to 300.000 s
Value in the on-delay timer
0.000 to 300.000 s
Value in the off-delay timer
Normal / Inverse –
Inversion operation of BI2 signal
Off/On
Switch for programmable operation in BI 3
0.000 to 300.000 s
Value in the on-delay timer
0.000 to 300.000 s
Value in the off-delay timer
Normal / Inverse –
Inversion operation of BI3 signal
.....
Off/On
Switch for programmable operation in BI
0.000 to 300.000 s
Value in the on-delay timer
0.000 to 300.000 s
Value in the off-delay timer
Normal / Inverse –
Inversion operation of BIn signal
- 1051 -
6F2S1914 (0.49)
Contents
.....
n
GRL200 (Soft 033 & 037)
Default
77
77
77
77
4
Off
0.000
0.000
Normal
Off
0.000
0.000
Normal
Off
0.000
0.000
Normal
.....
Off
0.000
0.000
Normal