Toshiba GR200 Series Instruction Manual page 1705

Line differential protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

Functional Data (6/7)
Phase Undervoltage Protection
1
st
, 2
nd
undervoltage threshold
Delay type
Drop-out/pick-up ratio
DTL delay
IDMTL Time Multiplier Setting TMS
Reset delay
Undervoltage block threshold
Undervoltage block delay
Phase to Phase Undervoltage Protection
1
, 2
undervoltage threshold
st
nd
Delay type
Drop-out/pick-up ratio
DTL delay
IDMTL Time Multiplier Setting TMS
Reset delay
Undervoltage block threshold
Undervoltage block delay
Under/Over Frequency Protection
1st - 4th under/overfrequency threshold
DTL delay:
Frequency UV Block
5.0 to 130.0V in 0.1V steps
DTL, IDMT, Original
100 to 120% in 1% steps
0.00 to 300.00s in 0.01s steps
0.010 to 100.000 in 0.001 steps
0.0 to 300.0s in 0.1s steps
5.0 to 20.0V in 0.1V steps
0.00 to 300.00s in 0.01s steps
5.0 to 130.0V in 0.1V steps
DTL, IDMT, Original
100 to 120% in 1% steps
0.00 to 300.00s in 0.01s steps
0.010 to 100.000 in 0.001 steps
0.0 to 300.0s in 0.1s steps
5.0 to 20.0V in 0.1V steps
0.00 to 300.00s in 0.01s steps
(Fnom − 10.00Hz) – (Fnom + 10.00Hz) in 0.01Hz steps
Fnom: nominal frequency
0.00 – 300.00s in 0.01s steps
40.0 – 100.0V in 0.1V steps
- 1682 -
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)

Advertisement

Table of Contents
loading

Table of Contents