Functional Data (4/7)
Breaker Failure (BF) Protection
Overcurrent element
BF timer for retry-trip of failed breaker
BF timer for related breaker trip
Non-directional and Directional Overcurrent Protection
1
, 2
, 3
, 4
Definite time overcurrent
st
nd
rd
th
threshold
1
, 2
, 3
, 4
Inverse time overcurrent
st
nd
rd
th
threshold
Direction characteristic
Polarising voltage
Characteristic angle
Delay type
Drop-out/pick-up ratio
DTL delay
IDMTL Time Multiplier Setting TMS
Reset type
Reset definite delay
Reset Time Multiplier Setting RTMS
Non-directional and Directional Earth Fault Protection
1
st
, 2
nd
, 3
rd
, 4
th
Definite time earth fault
threshold
1
st
, 2
nd
, 3
rd
, 4
th
Inverse time earth fault
threshold
Direction characteristic
Characteristic angle
Polarising voltage (3V0)
Delay type
Drop-out/pick-up ratio
DTL delay
IDMTL Time Multiplier Setting TMS
Reset type
Reset definite delay
Reset Time Multiplier Setting RTMS
0.1 to 2.0A in 0.1A steps (1A rating)
0.5 to 10.0A in 0.1A steps (5A rating)
50 to 500ms in 1ms steps
50 to 500ms in 1ms steps
0.02 to 50.00A in 0.01A steps (1A rating)
0.10 to 250.00A in 0.01A steps (5A rating)
0.02 to 5.00A in 0.01A steps (1A rating)
0.10 to 25.00A in 0.01A steps (5A rating)
Non Directional / Forward / Backward
1.0 V(fixed)
0 – 180 deg in 1 deg steps
DT / IEC-NI / IEC-VI / IEC-EI / UK-LTI / IEEE-MI / IEEE-
VI / IEEE-EI / US-CO2 / US-CO8 / Original
10 to 100% in 1% steps
0.00 to 300.00s in 0.01s steps
0.010 to 50.000 in 0.001 steps
Definite Time or Dependent Time
0.00 to 300.00s in 0.01s steps
0.010 to 50.000 in 0.001 steps
0.02 to 50.00A in 0.01A steps (1A rating)
0.10 to 250.00A in 0.01A steps (5A rating)
0.02 to 5.00A in 0.01A steps (1A rating)
0.10 to 25.00A in 0.01A steps (5A rating)
Non Directional / Forward / Backward
0 to 180° in 1° steps (3I0 lags for −3V0)
0.5 to 100.0V in 0.1V steps
DT / IEC-NI / IEC-VI / IEC-EI / UK-LTI / IEEE-MI / IEEE-
VI / IEEE-EI / US-CO2 / US-CO8 / Original
10 to 100% in 1% steps
0.00 to 300.00s in 0.01s steps
0.010 to 50.000 in 0.001 steps
Definite Time or Dependent Time
0.00 to 300.00s in 0.01s steps
0.010 to 50.000 in 0.001 steps