Tips (exercise)
If we have to have MIMIC exercise without actual breaker, a test CB can be possible for the
exercise. Figure 11 exemplifies a test CB made by PLC function. To create a test CB, see
Chapter PLC function
Test CB made with PLC logic for exercise
Time = 100ms or longer
BI3 at IO_SLOT1
S1_BI3
OUT
Stat
BI4 at IO_SLOT1
S1_BI4
OUT
Stat
Wiring diagram for test CB made with PLC function
Plus(+)
IO_SLOT2
BO3
BO4
Short
wires
IO_SLOT1
BI3
BI4
Figure 11 Test CB made with PLC function (example)
Note: In the example, spare BI3&4 and BO1&2 circuits (in red boxes) are used for
testing.
for more detail. Note that the test CB below is just an example.
Flip-flop
On delay timer
RS
SET
Q1
IN
RESET1
PT
Flip-flop
RS
SET
Q1
IN
RESET1
PT
Test CB for the
exercise
Made with PLC
- 1722 -
BO1 at IO_SLOT2
TON
S2_BO1
Q
IN
Stat
ET
BO2 at IO_SLOT2
TON
S2_BO1
Q
IN
Stat
ET
IO_SLOT2
IO_SLOT2
BO1
BO2
Short
wires
IO_SLOT1
BI1
BI2
Minus(-)
6F2S1914 (0.49)
IO_SLOT1
GRL200 (Soft 033 & 037)