Toshiba GR200 Series Instruction Manual page 1500

Line differential protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

IRIG SYNC menu
When the "IRIG SYNC" is set to On in Time Sync menu, the user can choose IRIG signal for
the synchronization.
IRIG SYNC
10:48
USE_BCDYEAR
Off
USE_LOCALTIME
Off
Figure 12.7-11 IRIGSYNC
Display format
(iv)
Display format of time in the IED can be selected in Display format screen. All time formats
will be displayed according to Date_fmt setting. The IED provides different formats to display
the date. Figure 12.7-12 shows display format menu:
Display Format sub-menu is composed of Date_fmt menu, Date_delimiter setting
Time_delimiter setting and Sec_delimiter setting.
Date format menu
Display Format
10:48
_Date_fmt
YYYYMMDD
Date_delimiter
-
Time_delimiter
:
Date_fmt
10:48
_YYYYMMDD
MMDDYYYY
DDMMYYYY
Figure 12.7-13 Date Format
(1) Set On if IRIG-B data is generated in IEEE C37.118/IRIG-B000
1/2
format. On the other hand, set Off if the IRIG-B is generated with
+
absence the C37.118.
+
Display Format
10:48
Date_fmt
YYYYMMDD
Date_delimiter
-
Time_delimiter
:
Figure 12.7-12 Display format menu
(1) Move cursor to "Date_fmt"; and press ENTER.
1/4
+
+
+
(2) Select desired format by moving cursor.
1/3
- 1477 -
6F2S1914 (0.49)
1/4
+
+
+
GRL200 (Soft 033 & 037)

Advertisement

Table of Contents
loading