IRIG SYNC menu
When the "IRIG SYNC" is set to On in Time Sync menu, the user can choose IRIG signal for
the synchronization.
IRIG SYNC
10:48
USE_BCDYEAR
Off
USE_LOCALTIME
Off
Figure 12.7-11 IRIGSYNC
Display format
(iv)
Display format of time in the IED can be selected in Display format screen. All time formats
will be displayed according to Date_fmt setting. The IED provides different formats to display
the date. Figure 12.7-12 shows display format menu:
Display Format sub-menu is composed of Date_fmt menu, Date_delimiter setting
Time_delimiter setting and Sec_delimiter setting.
Date format menu
Display Format
10:48
_Date_fmt
YYYYMMDD
Date_delimiter
-
Time_delimiter
:
Date_fmt
10:48
_YYYYMMDD
MMDDYYYY
DDMMYYYY
Figure 12.7-13 Date Format
(1) Set On if IRIG-B data is generated in IEEE C37.118/IRIG-B000
1/2
format. On the other hand, set Off if the IRIG-B is generated with
+
absence the C37.118.
+
Display Format
10:48
Date_fmt
YYYYMMDD
Date_delimiter
-
Time_delimiter
:
Figure 12.7-12 Display format menu
(1) Move cursor to "Date_fmt"; and press ENTER.
1/4
+
+
+
(2) Select desired format by moving cursor.
1/3
- 1477 -
6F2S1914 (0.49)
1/4
+
+
+
GRL200 (Soft 033 & 037)