Setting
Metering settings in MES (Function ID: 710001)
Setting item
Display Value
Power
Current
PF Sign
I-Valid Level
V-Valid Level
I-Display Unit
V-Display Unit
P-Display Unit
Q-Display Unit
S-Display Unit
Statistics settings in MES (Function ID: 710001)
Setting item
Wh-Display Unit
varh-Display Unit
Demand settings in MES (Function ID: 712001)
Setting item
Demand_period
Dead-band setting in MES (Function ID: 710001)
Setting item
ISD
VSD
P/Q/SSD
PFSD
FSD
Wh/varhSD
PhaseSD
PeriodSD
dVSD
Setting of Test in MES (Function ID: 710001)
Setting item
Commercial Test
Unit
Range
s
Primary/Secondary
–
Send/Receive
–
Lead/Lag
–
AP/AP+RP
–
0.10 to 5.00
%
0.10 to 5.00
%
A/kA
–
V/kV
–
kW/MW
–
kvar/Mvar
–
kVA/MVA
–
Unit
Range
s
kWh/MWh
–
kvarh/Mvarh
–
Unit
Range
s
1min / 5min /
10min / 15min /
–
30min / 60min
Unit
Range
s
0.00 to 50.00
%
0.00 to 50.00
%
0.00 to 50.00
%
0.00 to 1.00
–
0.00 to 50.00
%
0.0 to 999.9
–
0.0 to 90.0
deg
0 to 4
–
0.00 to 50.00
%
Unit
Range
s
OFF / ON
–
Contents
Display selection of primary or secondary
Power flow definition (Supply or absorb)
The angle compared with the voltage
Decision of the sign of the power factor
Cutting off small entering current
Cutting off small applied voltage
Current shown in Ampere or Kilo-Ampere
Voltage shown in Volt or Kilo-Volt
Active power shown in Kilo- or Mega-watt
Reactive power shown in Kilo- or Mega-var
Apparent power shown in Kilo- or Mega-
VA
Contents
Watt-hour shown in Kilo- or Mega-Wh
Var-hour shown in Kilo- or Mega-varh
Contents
Period of demand calculation
Contents
Sending Dead Band in current
Sending Dead Band in voltage
P/Q/S Sending Dead Band
PF Sending Dead Band
F Sending Dead Band
Wh/varh Sending Dead Band
Phase Sending Dead Band
Period of Sending Dead band
dV Sending Dead Band
Contents
Commercial Test Switch
- 1204 -
6F2S1914 (0.49)
Default
Notes
setting value
Primary
Send
Lead
AP+RP
4.00
0.30
kA
kV
MW
Mvar
MVA
Default
Notes
setting value
MWh
Mvarh
Default
Notes
setting value
10min
Default
Notes
setting value
5.00
0.60
5.00
0.02
0.50
1.0
0.5
0
0.60
Default
Notes
setting value
OFF / ON
GRL200 (Soft 033 & 037)