Toshiba GR200 Series Instruction Manual page 1395

Line differential protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

communication packets will not be received from the remote terminal. In order to
avoid the influence, we recommend the user to test bad receptions for a particular
IED using the GOSUBBLK function. As a result, testing will only affect the
particular IED under test i.e. all other terminals will not be influenced by the
tests.
Selection of a slave protocol
11.3.5
Figure 11.3-28 shows the sub menu to select a slave IEC61850 protocol. The user should select
IEC61850 using the [Slave Protocol]. Note that the user has to restart the IED (i.e., the user
has to switch the IED off and on) if the user has switched to a slave protocol from the others†.
Communication
10:48
1/3
LAN
USBCOM
SLAVE PROTOCOL
Figure 11.3-28 Slave protection for the IEC61850 (setting menu)
Note: This sample menu illustrates how to select the IEC 61850, so that we discuss
neither the inclusion of IEC103, DNP3.0, and Modbus nor the selection of those
protocols here. See Figure 11.1-1 to check the inclusion of the protocols in the IED.
How to supervise in 61850 communication
11.3.6
The IED can detect errors on the IEC 61850 communication. The feature is provided separately.
Automatic supervision: Supervision of setting data [Commslv error]
(See Chapter
SLAVE PROTOCOL
10:48
Slave Protocol
>
IEC61850
>
>
- 1372 -
6F2S1914 (0.49)
SLAVE PROTOCOL
1/1
10:48
+
IEC61850
IEC103†
DNP3.0†
Modbus†
GRL200 (Soft 033 & 037)
1/4
)

Advertisement

Table of Contents
loading

Table of Contents