GOOSE receiving block (GOSUBBLK)
(ii)
This is used for receiving or rejecting GOOSE subscription information from another IED for
testing bad reception. See Chapter
Test flag cancel (S-TestFlagCancel)
(iii)
Test flag in the communication packet will be removed unconditionally, when On is set for
setting [Test flag].
Test for all communication (TestFlag-EN)
(iv)
Setting [TestFlag-EN]=On allows to set test flags at all communication protocol (see Chapter
User interface: Test-submenu
Test for relay application
14.4.2
Auto monitoring function (A.M.F)
(i)
Issuing alarms will be blocked when Off is set for [A.M.F]. For the content about the monitoring
function, see Chapter
Test of cold load protection (CLP-Test)
(ii)
STATE0 or STATE3 will be selected temporally, if STATE0 or STATE3 is set for setting [CLP-
TEST]. See Chapter
Local test (Local-test)
(iii)
When [Local-test]=On, '1' is set at Local test bit of SCOM4 so that zero-ampere control is
executed. For more information, see Chapter
Local loop test (Loop-test)
(iv)
If [Loop-test]=On, loop-back test is executed locally See Chapter
Communication application
Open test (OPEN 1/OPEN 2)
(v)
When setting [OPEN 1/2]=On, the communication channel#1/2 will be cut locally. Channel
arrangements are discussed in Chapter
Stub protection test (DIFL-STUB-Test)
(vi)
Stub test will run by setting [DIFL-STUB-Test]=On. See Chapter
operations for 1.5CB arrangement: Stub protected by DIFL
Communication protocol: IEC 61850 communication
).
Automatic supervision function
Relay application: Cold load protection
for more details.
Relay application: Communication application
- 1510 -
.
for more detail.
Relay application: Communication application
.
6F2S1914 (0.49)
.
Relay application:
.
Relay application: DIFL