Signal
4.11.8
Signal monitoring points in ASEQ01
ASEQ(Function ID: 523001)
Element ID
000D001F40
000D011001
000D011D90
310D011D00
310D011D01
800D011D51
800D011D52
800D011D53
800D011D54
800D011D55
800D011D56
800D011D57
800D011D58
810D011F51
820D011F50
000D0D1001
000D0D1D90
310D0D1D00
310D0D1D01
800D0D1D51
800D0D1D52
800D0D1D53
800D0D1D54
800D0D1D55
800D0D1D56
800D0D1D57
800D0D1D58
810D0D1F50
Connection points in PLC logic in ASEQ01
ASEQ(Function ID: 523001)
Element ID
820D01ED50
800D01EDF2
820D10ED50
Mapping point in ASEQ01
ASEQ(Function ID: 523001)
Element ID
700D016D08
Note: In the table above, the user will only find Element IDs and their names for the 1
Name
ASEQ_MULTI_SEL
ASEQ01_ACC_EXEC
ASEQ01_STSELD
ASEQ01_MMC_ST
ASEQ01_LCD_ST
ASEQ01_SC_OWS
ASEQ01_SC_RCC
ASEQ01_SC_RMT
ASEQ01_SC_LCD
ASEQ01_EC_OWS
ASEQ01_EC_RCC
ASEQ01_EC_RMT
ASEQ01_EC_LCD
ASEQ01_EXEC_STOP
ASEQ01_EXEC_START
EMERSTOP_ACC_EXEC
EMERSTOP_STSELD
EMERSTOP_MMC_ST
EMERSTOP_LCD_ST
EMERSTOP_SC_OWS
EMERSTOP_SC_RCC
EMERSTOP_SC_RMT
EMERSTOP_SC_LCD
EMERSTOP_EC_OWS
EMERSTOP_EC_RCC
EMERSTOP_EC_RMT
EMERSTOP_EC_LCD
EMERSTOP_EXEC_STOP
Name
ASEQ01IN_TMP_28
ASEQ01_EXEC_RESET
EMERSTOPIN_TMP_28
Name
ASEQ01_CONTROL_REQ
- 1008 -
Description
Status flag to not be selected for multiple operations
Reception state of the automatic sequence instruction command
ASEQ01 selected signal(stSeld) for SAS
ASEQ01 state for MIMIC
ASEQ01 state for LCD
ASEQ01 select command by OWS(HMI)
ASEQ01 select command by RCC
ASEQ01 select command by Remote
ASEQ01 select command by LCD
ASEQ01 execute command by OWS(HMI)
ASEQ01 execute command by RCC
ASEQ01 execute command by Remote
ASEQ01 execute command by LCD
Commencing command for automatic sequence
Stop command for automatic sequence
Reception state of an emergency signal to stop the operation
EMERSTOP selected signal (stSeld) for SAS
EMERSTOP state for MIMIC
EMERSTOP state for LCD
EMERSTOP select command from OWS(HMI)
EMERSTOP select command from RCC
EMERSTOP select command by Remote
EMERSTOP select command from LCD
EMERSTOP execute command from OWS(HMI)
EMERSTOP execute command from RCC
EMERSTOP execute command by Remote
EMERSTOP execute command from LCD
Commencing command for emergency stop
Description
Reception of control right for ASEQ01
Reception of reset signal for ASEQ01 operation
EMERSTOPIN_TMP_28
Description
ASEQ01 control command received. (Mapping Data)
6F2S1914 (0.49)
st
GRL200 (Soft 033 & 037)

Advertisement