Binary Inputs
Input circuit DC voltage
Capacitive discharge immunity
Maximum permitted voltage
Power consumption
Binary Outputs
Fast operating contacts
Make and carry
Break
Operating time
Semi-fast operating contacts
Make and carry
Break
Operating time
Auxiliary contacts
Make and carry
Break
Operating time
Hybrid contacts (10 A breaking)
Make and carry
Break
Operating time
Durability
Measuring input capability
Full scale
Standard current input
Sensitive current input
Voltage input
Sampling rate
Frequency response
24/48/60Vdc
(Operating range: 19.2 – 72Vdc),
110/125/220/250Vdc (Operating range: 88 – 300Vdc)
Note: Pick-up setting is available in BI2 (range: 18V – 222V)
10μF charged to maximum supply voltage and discharged
into the input terminals, according to ENA TS 48-4 with an
external resistor
72Vdc for 24/48/60Vdc rating,
300Vdc for 110/250Vdc rating
 0.5W per input at 220Vdc
5A continuously
30A, 290Vdc for 0.2s (L/R=5ms)
0.15A, 290Vdc
(L/R=40ms)
Typically 3 ms
8A continuously
30A, 240Vdc for 1s (L/R=5ms)
0.1A at 250Vdc
(L/R=40ms)
0.2A at 125Vdc
(L/R=40ms)
Typically 6 ms
8A continuously
30A, 240Vdc for 1s (L/R=5ms)
0.1A at 250Vdc
(L/R=40ms)
0.2A at 125Vdc
(L/R=40ms)
Typically 8 ms
8A continuously
10A, 220Vdc for 0.5s (L/R=5ms)
10A, 220Vdc
(L/R=20ms)
10A, 110Vdc
(L/R=40ms)
1 ms
≥ 10,000 operations (loaded contact)
≥ 100,000 operations (unloaded contact)
≥ 60A (1A rating) or 300A (5A rating)
≥ 3A (1A rating) or 15 A (5A rating)
≥ 200V
48 samples / cycle
< 5% deviation over range 16.7Hz to 600Hz