Functional Data (2/7)
Phase Fault Distance Measuring Element
Z*-Mho.Reach, Z*-X.Reach and Z*-R.Reach
(Z1S, Z1XS, Z2S, Z3S, Z4S, Z5S, ZCSF,
ZCSR))
Characteristic angle
Z*-Mho.Angle and Z*-R.Angle (Z1S, Z1XS,
Z2S, Z3S, Z4S, Z5S, ZCSF, ZCSR))
Z*- DirX.Angle and Z*-DirR.Angle ((Z1S,
Z1XS, Z2S, Z3S, Z4S, Z5S, ZCSF, ZCSR))
ZSF-X.GrAngle1 and ZSR-X.GrAngle1
ZSF-X.GrAngle2 and ZSR-X.GrAngle2
Trip time characteristics (IEC60255-121)
Earth Fault Distance Measuring Element
Z*-Mho.Reach, Z*-X.Reach and Z*-R.Reach
((Z1G, Z1XG, Z2G, Z3G, Z4G, Z5G, ZCGF,
ZCGR)
Characteristic angle
Z*-Mho.Angle and Z*-R.Angle (Z1G, Z1XG,
Z2G, Z3G, Z4G, Z5G, ZCGF, ZCGR)
Z*- DirX.Angle and Z*-DirR.Angle (Z1G,
Z1XG, Z2G, Z3G, Z4G, Z5G, ZCGF, ZCGR)
ZGF-X.GrAngle1 and ZGR-X.GrAngle1
ZGF-X.GrAngle2 and ZGR-X.GrAngle2
Trip time characteristics (IEC60255-121)
Timer Setting
Time setting of Z1S, Z1XS, Z2S, Z3S, Z4S,
Z5S, Z1G, Z1XG, Z2G, Z3G, Z4G, Z5G
Overcurrent Element for Fail-safe
Overcurrent elements Z*_OCFS for
supervision distance measuring elements
((Z1S, Z1XS, Z2S, Z3S, Z4S, Z5S, Z1G, Z1XG,
Z2G, Z3G, Z4G, Z5G)
0.10 to 500.00Ω in 0.01Ω steps (1A rating)
0.01 to 100.00Ω in 0.01Ω steps (5A rating)
30° to 90° in 1° steps
0° to 60° in 1° steps
0° to 45°in 1° steps
45° to 90° in 1° steps
See page 1686
0.10 to 500.00Ω in 0.01Ω steps (1A rating)
0.01 to 100.00Ω in 0.01Ω steps (5A rating)
30° to 90° in 1° steps
0° to 60° in 1° steps
0° to 45°in 1° steps
45° to 90°in 1° steps
See page 1686
0.00 to 100.00s in 0.01steps
0.02 to 5.00A in 0.01A steps (1A rating )
0.10 to 25.00A in 0.01A steps (5A rating)
- 1678 -