Toshiba GR200 Series Instruction Manual page 1330

Line differential protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

Communication failure (Com fail)
10.5.4
The transmission between two IEDs is also monitored. If the error is detected for ten seconds,
the communication failure is issued.
Error level
(i)
Generally, the default error level is set at level 2 (Serious error (Comm)), but the user can
program the level using settings [CHK_CM_FAIL1:Lvl] and [CHK_CM_FAIL2:Lvl]; then, set On
for the setting [CHK_CM_FAIL1:Sw] and [CHK_CM_FAIL2:Sw]. The manufacture sets ten (10)
seconds to detect the failure; it is reset in 12 ssp (i.e., 12×48×Power_system_frequency (Hz))
when the failure is cleared.
Error message
(ii)
When the function operates and detects error, an error message can be shown at the LED and
the LCD screen.
Table 10.5-9 Error messages provided by the supervisor in CHK_CM_FAIL
Message and level
ComX fail
Error level
†Note: Level 2 is set as default, but the user can change the error level above using the
settings [CHK_CM_FAIL*:Lvl].
Table 10.5-10 Detailed information in CHK_CM_FAIL
Code No.
N/A
Meaning of the information
Detection of an error located at X†
Serious error (Level 2) †
Meaning of the detailed information
(No information is displayed)
- 1307 -
6F2S1914 (0.49)