1-2. Type using compression terminals and 24-60 Vdc
IED case structure
DC rated voltage
Figure-11.B illustrates external connection around the power supply module (PWS). During dielectric
voltage testing, three short-wires attached on the PSW shall be carefully handled; follow the below
instructions (1), (2) and (3).
(1) The short-wire between terminal screw No.35 and No.37
Remove the short-wire for undertaking the dielectric voltage test. If the short-wire is not
removed, the IED will be damaged.
After the test, reconnect the short-wire to the original positons.
(2) The short-wire between terminal screw No.38 and FG
Never remove the short-wire. If the short-wire is removed, the IED will be damaged.
(3) The short-wire between terminal screw No.36 and FG
Never remove the short-wire. If the short-wire is removed, the IED will be damaged.
(1)
(2)
(3)
Figure-11.B A Short-wires, around the PWS, for Type using compression terminals and 24-60Vdc