WAGO 765-1103/100-000 Manual page 39

16-channel digital output; profinet; 24 v dc; 2.0 a; 8 × m12 connection
Table of Contents

Advertisement

765-1103/100-000
Planning
Figure 6: Connect Example with Individual Power Supply (module image may vary)
One digital input/output with a current consumption of max. 2 A is connected to connec-
tions X01 to X04 of the module. The module's current consumption is 0.2 A.
Supply cable 1 then has a total current consumption of 2 × 2 A + 0.2 A = 4.2 A, and sup-
ply cable 2 has a total current consumption of 2 × 2 A = 4.0 A.
These do not exceed the maximum permissible value of 16 A per supply cable and are
thus permissible.
Example of a Power Supply Group via PWR OUT
If you connect another device to the PWR OUT (X32) power supply output, this forms a
supply group. The maximum permissible current feedthrough that this module can require
is 16 A – 4.2 A = 11.8 A for supply cable 1 (1L) und 16 A – 4.0 A = 12 A for supply ca-
ble 2 (2L).