Diagnostics
Number
(hex)
0x0101
0x0102
0x0103
0x0104
0x0105
0x0106
0x0107
0x0108
0x0109
0x010A
0x010B
98
Product manual | Version: 2.2.0
16DO FLD PN DC 24V 2.0A
Alarm
Description
Overvoltage
Overvoltage in supply line 1L
The supply line has exceeded the limiting
value for the maximum voltage.
Overtemperature
Overtemperature
The device temperature has exceeded the
upper limiting value.
Overload
Overload in supply line 1L
The total current in supply line 1L has ex-
ceeded the upper limiting value.
Overload, 2L
Overload in supply line 2L
The total current in supply line 1L has ex-
ceeded the upper limiting value.
Undertemperature
Undertemperature
The device temperature has fallen below
the lower limiting value.
Undervoltage, 2L
Undervoltage in supply line 2L
The power supply for supply line 2L has
fallen below the limiting value for the mini-
mum voltage.
Overvoltage, 2L
Overvoltage in supply line 2L
The power supply for supply line 2L has ex-
ceeded the limiting value for the maximum
voltage.
Forcing operating mode
Forcing operating mode active (activated
active
by Web client or OPC UA client)
Short circuit on pin 4
Short circuit detected on pin 4
Short circuit on pin 2
Short circuit detected on pin 2
Short circuit on pin 1
Short circuit detected on pin 1.
765-1103/100-000
Corrective Action
Check supply voltage
Eliminate external heat
source or overload.
Eliminate overload.
Eliminate overload.
Thermally insulate the de-
vice
Check supply voltage
Check supply voltage
The Web client or OPC UA
client should exit forcing op-
erating mode as soon as
forcing is no longer needed.
Eliminate short circuit.
Eliminate short circuit.
Eliminate short circuit.