10.3.3.1.10.3 Enabling Forcing
Requirements
• You must have an OPC UA client.
• You must know the username and password, and this user must have permission to
execute methods.
• You must have already established a connection to the I/O module.
Step-by-Step Instructions
1. In the Address Space window, open the context menu: Root > Objects > De-
viceSet > [device name] > Forcing > GetForcingID
2. In the context menu, select Call.
ð The Call GetForcingID on Forcing window appears.