Outputs; Timers - Deif SGC 410 User Manual

Single genset controller
Table of Contents

Advertisement

Level 2
(0-5 V) Calibration Table

6.2.5 Outputs

Table 6.17
Outputs # (OUT #)
Level 2
Source
(SOURCE)
On Activation
(ON ACTIVATION)

6.2.6 Timers

Table 6.18
Cranking (CRANKING TIMERS)
Level 2
Crank Hold Time
(CRANK HOLD TIME)
Crank Rest Time
(CRANK REST TIME)
Manual Start Delay
(MANUAL START DELAY)
Auto Start Delay
(AUTO START DELAY)
Table 6.19
Start/Stop (START/STOP TIMER)
Level 2
Safety Monitoring Delay
(SAFETY MONITOR DELAY)
Mains Detect Delay
(MAINS DETECT DELAY)
Alternator Detect Delay
(ALT DETECT DELAY)
Warm-Up Delay
(WARM-UP DELAY)
Return To Mains Delay
(RETN-TO-MAINS DELAY)
Engine Cooling Time
(ENG COOL TIME)
Stop Action Time
(STOP ACTION TIME)
Additional Stopping Time
USER MANUAL 4189341243A UK
Range
Warning
Electrical Trip
Shutdown
Voltage: 0 to 5 V
Value: 0 to 1000
Range
See Digital output source selection in this document
Energise
De-energise
Range
1 to 15 s
2 to 60 s
0 to 300 s
0 to 300 s
Range
10 to 60 s
1 to 300 s
1 to 30 s
0 to 60 s
0 to 600 s
0 to 300 s
10 to 120 s
0 to 120 s